background image

Q7055C HONEYWELL METER POINT CONNECT

39-00002

2

SPECIFICATIONS

Models:

Q7055C1053 Honeywell Meter Point Connect Model M1.

Q7055C1055 Honeywell Meter Point Connect Model M2.

Electrical Ratings:

Supply Voltage: 24 VAC, 50 to 60 Hz, 24 VDC (external power

supply required).

Power Consumption: 8 VA.

Temperature Ratings:

Operating: 32° F to 122° F (0° C to 50° C).

Storage: -13° F to +185° F (-25° C to +85° C).

Humidity Ratings:

5 to 93% RH, non-condensing.

System Data:

Processor: 32-bit high-speed microprocessor.

Data Transfer: 10/100 Mbit/sec., 802.3 Ethernet.

LAN Interface: 10/100BaseT (RJ-45).

Field Bus: [CH1], [CH1,CH2] RS-485 DC Coupled to M-Bus

level converter.

Device Interface: Serial RS-232.

Memory Type: SDRAM, NOR & NAND Flash.

MTBF: > 100,000 hours.

Safety:

Protection Standard: IP20 according to EN60529.

Protection Class: II according to EN60730-1.

Flame Retardant: V0 according to UL 94.

Dimensions (W x H x D): 8-13/16 in. (224 mm) x 2-13/16 in.

(72 mm) x 7-13/16 in. (199 mm).

Weight: 2.0 lb (0.9 kg).

Approvals:

EN61000-6-4; 2007

EN61000-6-2; 2005

Low Voltage Directive 2006/95/EC

RTTE Directive 1999/5/EC

EMC Directive 2004/108/EC

RoHS Directive 2011/65/EU

WEEE Directive 2002/96/EC

Energy Management Equipment: UL916

FCC Part 15 Class A

Additional Equipment:

Model EMSA240075, P/N EMSA240075-P5P-SZ 120/240

Vac, 50/60 Hz input, 24 Vdc, 0.75 A output, Class 2.

50/60 Hz input, 24 Vdc, 0.75 A output, Class

2, Honeywell part number 50050810-002 (included).

AC Power Supply: 120 Vac 50/60 Hz input, 24 Vac output

50008533-001/U Wall Hanging Accessories Kit.

DC Power supply: CUI Model No. SMI18-24-V-P5, 120/ 240

Vac, 50/60 Hz input, 24 Vdc, 0.8 A output, Class 2.

Accessories

Honeywell Meter Point Connect devices provide RS485 signal

interface for bus connection(s), and require use of level

converter device(s) for conversion of RS485 levels to M-Bus

voltage levels for connection to meters. Following level

converters have been tested for use with MPC devices:

RS485 to M-Bus Converters:

Relay Model PW60: RS485 > M-Bus level converter for up to

60 devices.

ADFweb Model HD67022M-20: RS485 > M-Bus level

converter for up to 20 devices.

RS232 TO M-BUS CONVERTERS:

(These are used with RS485 > RS232 converters listed

below) 

Relay Model PW3: RS232 > M-Bus level converter for up to 3

devices

Relay Model PW20: RS232 > M-Bus level converter for up to

20 devices

RS485 TO RS232 CONVERTERS:

MOXA Model TCC-108I: RS485 > RS232 converter. 

B&B Model 4WSD90TB: RS485 > RS232 converter.

ICS Model I-7520R: RS485 > RS232 converter.

Connecting multiple M-Bus level Converters on MPC

single M-Bus Channel:

Fig. 2. Connecting multiple M-Bus Converters

In order to connect more meters to an M-Bus port than 

supported by a single converter device, additional M-Bus 

converter(s) can be connected to the RS485 M-Bus on M1 or 

M2 devices in parallel with the existing converter.  Only the 

converters that directly convert between RS-485 and M-Bus 

(and do not use an intermediate RS232 type connection) can 

be connected in this manner. The end-of-line (EOL) 

terminations and biasing for each device connected to the 

RS485 M-Bus (CH1 or CH2) as well as the port switch 

settings for MPC should be set in accordance with location of 

each device on the bus. 

M25412A

MPC M-BUS CH1 or CH2

M-BUS SUPPORTED

SUB-METERING DEVICES

M-BUS LEVEL

CONVERTER

LC1

RS485

LC1

RS485

LC1

RS485

Содержание Q7055C1053

Страница 1: ...ice providers The Meter Point communicates to sub metering devices via a M Bus level converter using M Bus standards EN13757 3 and EN1434 3 With its combination of scalable performance density and low per port pricing the MPC allows network layer capabilities to be extended to a much wider range of network configurations and environments Customers can now gain the advantages of high performance ne...

Страница 2: ...8 24 V P5 120 240 Vac 50 60 Hz input 24 Vdc 0 8 A output Class 2 Accessories Honeywell Meter Point Connect devices provide RS485 signal interface for bus connection s and require use of level converter device s for conversion of RS485 levels to M Bus voltage levels for connection to meters Following level converters have been tested for use with MPC devices RS485 to M Bus Converters Relay Model PW...

Страница 3: ...0004 Q7055C1053 MPC M1 Single M Bus and Q7055C1055 MPC M2 Dual M Bus MPC Router Installation Guide Form no 39 00005 Q7055C1053 MPC M1 Single M Bus and Q7055C1055 MPC M2 Dual M Bus Soft ware Release Bulletin WIRING CAUTION Shock Hazard Removal of the MPC cover can result in electrical shock Do not remove cover There are no user serviceable parts inside Location and Mounting The MPC device is intend...

Страница 4: ...3 pole Phoenix connectors that are marked for power 2 Fasten them with a small screwdriver 3 Connect a chassis ground to the third position on this connector as marked NOTE The polarity of the 3 pole Phoenix power connector for DC power supplies is don t care Field Bus Connection Ch1 Ch2 The 2 pole Phoenix connectors included are required for connecting the field bus Field bus connection can be co...

Страница 5: ...ection describes the pin layout for the RJ 45 connector Most Ethernet local area networks use twisted pair wiring 10 100BaseT networks are physically laid out in a star topology where each piece of equipment on the network is connected to a central switch The wiring is connected to devices using a plug that resembles a phone jack called RJ 45 See Table 2 on page 5 for details Connect MPC to Switch...

Страница 6: ...h continuously When MPC Bootloader starts to run the Red LED starts to flash When the application firmware begins to run the Green LED starts flashing 4 CH1 Bus Channel 1 activity display This display contains two green LEDs one showing the MPC receive activity Rx and the other showing the MPC transmit activity Tx 5 CH2 Bus Channel 2 activity display This display contains two green LEDs one showin...

Страница 7: ...eld bus channel 1 connection electrically isolated meets EMC and FCC requirements Field Bus wiring is described in the Field Bus Connection Ch1 Ch2 section 11 AC DC IN 24V Power connector for 24 VAC 50 Hz to 60 Hz or 24 VDC power supplies and chassis ground An external power supply is required See the Power Connection section of this document for details 12 RS 232 9 pin SUB D male RS 232 connector...

Страница 8: ...eywell International Inc 39 00002 A A Rev 04 16 Printed in Germany Automation and Control Solutions Honeywell GmbH Boeblinger Straße 17 71101 Schoenaich Germany Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 www honeywell com buildingsolutions ...

Отзывы: