background image

7-101004-01 

1

NS2 Configuration Guide

Contents

Description  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1
Specifications  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1

Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1

Backup Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1

Secondary Backup Battery. . . . . . . . . . . . . . . . . . . . . . . .  1

Reader & Aux Power . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1

Reader Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2

Supervised Input Wiring  . . . . . . . . . . . . . . . . . . . . . . . . .  2

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

Enclosure Specifications  . . . . . . . . . . . . . . . . . . . . . . . . .  4

Communications & Wiring . . . . . . . . . . . . . . . . . . . . . . .  4

DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Connection Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

Configuration Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

RS-232 Connection  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

RS-485 Connection  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

NSLAN1 Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

LANSRL100 Connection. . . . . . . . . . . . . . . . . . . . . . . .  10

LANSRLU1 Connection . . . . . . . . . . . . . . . . . . . . . . . .  11

Lease Line Modem Connection . . . . . . . . . . . . . . . . . . .  12

RS-485 Short Haul Modem Connection  . . . . . . . . . . . .  13

RS-232 Short Haul Modem Connection  . . . . . . . . . . . .  14

M-9600 Dial-up Modem, RS-485 Connection  . . . . . . .  15

M-56K Dial-up Modem, RS-485 Connection . . . . . . . .  16

Fiber Converter to RS-485 Connection . . . . . . . . . . . . .  17

485-PCI/NS2 Panel Connection Detail . . . . . . . . . . . . .  18

Frequently Asked Questions

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Description

The NS2 is a two reader panel providing access control for up 
to two doors through the use of Wiegand readers.

The NS2 may be used as a standalone panel with independent 
card and transaction storage or, with a software upgrade, as a 
fully monitored online access control device. Communication 
to the front-end computer is achieved through an RS-232 serial 
cable (included with installation kit) or an optional RS-485 
interface. Each RS-485 interface is capable of communicating 
with up to 31 panels.

The NS2 is designed for tile mount using the ENC10 enclo-
sure. The I/O terminals are organized by operational utility 
with connectors for power and RS-485 communications 
located on the lower right followed from right to left by the 
relays, auxiliary power, door control inputs, and readers. The 
Tamper and External Power Fail terminal are located at the left 
edge above the main line of connectors.

Specifications

Power

AC Non-Polarized:

16.5 VAC utilizing a UL-listed 50 VA Class 2 transformer 
(TB9-4 AC+/TB9-5 AC–)

or 

DC Polarized:

24 VDC, 1.25 Amp (TB9-4 DC+/TB9-5 DC–)

Power Wire
Two-wire, 18 AWG, shielded cable.

Backup Battery

Casil 12 VDC (NCI Part #: BAT-3) 4Ah, sealed acid/lead 
backup battery (J6 DC+/J7 DC–)

Backup battery will provide 2.5 hours of standby backup 
power.

Charging voltage: 13.7 +/– 0.1 VDC

NOTE:

The NS2 panel has deep discharge protection built in for the 

protection of the battery and will only utilize a backup battery down to 
10.2 VDC before the NS2 shuts down. Backup battery should be 
replaced 2 to 2.5 years: more often if panel has a high rate of backup 
use.

Secondary Backup Battery

The NS2 panel memory is backed up using a super capacitor 
for one week in the absence of power or a backup battery. The 
super capacitor will backup panel memory and real-time clock 
and does not require maintenance or replacement.

Reader & Aux Power

Reader and AUX power is supplied at 10.8-12.7 VDC with a 
maximum current of 600 mA.

Five volt (5 VDC) readers require five-volt regulators (North-
ern part no. 5VRDREG)

Maximum draw is less then 600 mA: (Reader 1+ Reader 2 + 
Aux Power) < 600 mA.

NOTE:

Aux power must not be used to power locks.

Содержание NS2

Страница 1: ... are organized by operational utility with connectors for power and RS 485 communications located on the lower right followed from right to left by the relays auxiliary power door control inputs and readers The Tamper and External Power Fail terminal are located at the left edge above the main line of connectors Specifications Power AC Non Polarized 16 5 VAC utilizing a UL listed 50 VA Class 2 tra...

Страница 2: ...points located on the following terminals NOTE Tamper and External Power Fail are supervised and capa ble of being used as additional inputs if the default functionality is not needed NOTE The wire used for the inputs should be shielded and cannot exceed 30 ohms over the entire length of the cable Remember that the distance from the panel to the door must be doubled to determine the total resistan...

Страница 3: ...tive load including door strikes and magnetic locks it should not be used for low current dry circuit applications NOTE Switching of inductive loads can cause EMI Electromag netic Interference which may interfere with the normal operation of other equipment To minimize premature contact failure and increase system reliability contact circuit protection such as the S 4 suppressor is required Locate...

Страница 4: ... RS 485 9 pin to CPU 31 4K 1219 5 Network NSLAN1 Cobox Unit RS 232 1 NS2 panel per NSLAN1 64 max IP connections per system 328 100 LANSRL100 N 485 PCI 2L Ethernet to RS 485 31 NS2 panels per 485 interface 64 max IP connections per system 328 4K 100 1219 6 LANSRLU1 N 485 PCI 2L Ethernet to RS 485 31 NS2 panels per 485 interface 64 max IP connections per system 328 4K 100 1219 6 Modems M 9600 LA LO ...

Страница 5: ...ON OFF Address 13 OFF ON ON ON OFF Address 14 ON ON ON ON OFF Address 15 OFF OFF OFF OFF ON Address 16 ON OFF OFF OFF ON Address 17 OFF ON OFF OFF ON Address 18 ON ON OFF OFF ON Address 19 OFF OFF ON OFF ON Address 20 ON OFF ON OFF ON Address 21 OFF ON ON OFF ON Address 22 ON ON ON OFF ON Address 23 OFF OFF OFF ON ON Address 24 ON OFF OFF ON ON Address 25 OFF ON OFF ON ON Address 26 ON ON OFF ON O...

Страница 6: ...Y3 COM RELAY3 NC RELAY4 NO RELAY4 COM RELAY4 NC RS485 RS485 RS485 COM AC DC AC DC LED DATA 0 DATA 1 12VDC RDR TMPR AUX 5 ENC TMPR AUX 8 COMMON PWR FAIL AUX 7 BROWN GREEN WHITE BLACK RED VARIES BROWN GREEN WHITE BLACK RED VARIES PWR ON LED PWR ON LED READER1 READER2 TB1 TB2 TB3 TB4 TB5 TB6 TB9 TB8 TB7 RELAY LEDS SYSTEM STATUS LEDS POWER LED DIPSWITCHES INPUT 1 INPUT 2 INPUT 3 INPUT 4 RELAY1 RELAY2 ...

Страница 7: ...Disable S7 ON 57 600 Baud Rate S8 S10 OFF NStar Server COM 1 COM 2 NS2 Panel EG NS2 Panel CBL50 RS 232 50 ft Max CBL50 RS 232 50 ft Max Request To Send RTS CBL50 RS 232 Signal Ground GND Receive Data RXD Transmit Data TXD Clear To Send CTS RS 232 DB9 RJ 45 8 5 2 3 7 2 3 4 5 7 9 Pin COM 1 or COM 2 to RJ 45 on NS2 Panel EG It is recommended to earth ground EG each NS2 enclosure individually ...

Страница 8: ...ettings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 OFF 485 EOL EG EG EG EG DIP Switch Settings S1 ON S2 ON S3 ON S4 ON S5 ON S6 OFF Ack Nak on S7 ON S8 OFF 19 200 Baud Rate DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL 4 000 ft 1 200 m max 24 AWG 2 twisted pairs with shield 120 ohm 23 pf NCI part no NCP24...

Страница 9: ...seT CAT 5 328 Ft Max 100BaseT CAT 5 328 Ft Max EG NSLAN1 must be programmed with a static IP address See NSLAN1 product documentation for programing instructions DIP Switch Settings S1 S5 Panel Address S6 OFF RS 485 Disable S7 ON 57 600 Baud Rate S8 S10 OFF HUB It is recommended to earth ground EG each NS2 enclosure individually EG NIC NS2 Panel NSLAN1 installed NS2 Panel NSLAN1 installed ...

Страница 10: ...e of cable EG EG EG It is recommended to earth ground EG each NS2 enclosure individually DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 OFF 485 EOL S1 ON S2 ON S3 ON S4 ON S5 ON S6 OFF Ack Nak on S7 ON S8 OFF 19 200 Baud Rate 4 000 ft 1 200 m m...

Страница 11: ...8 OFF 19 200 Baud Rate NS2 Panel NS2 Panel EG Only Earth Ground EG one side of cable EG EG EG It is recommended to earth ground EG each NS2 enclosure individually DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 OFF 485 EOL 4 000 ft 1 200 m max 2...

Страница 12: ...Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 OFF 485 EOL It is recommended to earth ground EG each NS2 enclosure individually Female 9 Pin Male 25 Pin TX 3 2 TX Comm 5 7 Comm RX 2 3 RX RS 232 50 Ft COM Port Null Modem Cable Cable 9 25 Pin Male 9 ...

Страница 13: ...te It is recommended to earth ground EG each NS2 Enclosure individually Only Earth Ground EG one side of cable EG EG EG Refer to 485 PCI NS2 Panel Connection Detail diagram RS232 Cable 2 TX 3 RX DTE Straight 2 TX 3 RX 7 GND DCE Null 2 RX 3 TX 7 GND PC DB 9 MODEM 5 Comm or RS232 Cable 2 TX 3 RX DTE Straight 2 TX 3 RX 7 GND DCE Null 2 RX 3 TX 7 GND PC DB 9 MODEM 5 Comm or Male 9 Pin Male 25 Pin 5279...

Страница 14: ... OFF RS 485 Disable S7 ON 57 600 Baud Rate S8 S10 OFF It is recommended to earth ground EG each NS2 enclosure individually SHM B ASYNC Short Haul Modem SHM B ASYNC Short Haul Modem Male 9 Pin Male 25 Pin RS 232 50 Ft Max RS232 Cable 2 TX 3 RX DTE Straight 2 TX 3 RX 7 GND DCE Null 2 RX 3 TX 7 GND PC DB 9 MODEM 5 Comm or RS232 Cable 2 TX 3 RX DTE Straight 2 TX 3 RX 7 GND DCE Null 2 RX 3 TX 7 GND PC ...

Страница 15: ...ndividually DIP Switch Settings S1 ON S2 ON S3 ON S4 ON S5 ON S6 OFF Ack Nak on S7 ON S8 OFF 19 200 Baud Rate Female 9 Pin Male 25 Pin TX 3 2 TX Comm 5 7 Comm RX 2 3 RX Female Male DB 9 DB 25 Connectors DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bia...

Страница 16: ...round EG one side of cable EG EG EG EG DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 OFF 485 EOL DIP Switch Settings S1 ON S2 ON S3 ON S4 ON S5 ON S6 OFF Ack Nak on S7 ON S8 OFF 19 200 Baud Rate Female 9 Pin Male 25 Pin TX 3 2 TX Comm 5 7 Comm...

Страница 17: ... 485 Drain Wire Floating TB9 3 RS485 Comm Fiber Wire 10 000 Ft TB9 1 RS485 TB9 2 RS485 TB9 3 RS485 Comm NS2 Panel RS 485 Drain not connected here connected at panel side RS 485 Comm RXD PWR TXD RS 485 Positive RS 485 Negitive Fiber TXD Fiber RXD FC485 RS 485 Fiber Converter NS2 Panel NS2 Panel RS 485 Comm RXD PWR TXD RS 485 Positive RS 485 Negitive Fiber TXD Fiber RXD FC485 RS 485 Fiber Converter ...

Страница 18: ...CP2441 TN 485 B L A C K G R E E N RED WH ITE C O M M O N DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 ON 485 EOL DIP Switch Settings S1 S5 Panel Address S6 ON RS 485 Enable S7 N A Baud Rate S8 S9 OFF Bias S10 OFF 485 EOL DIP Switch Settings S1 ON S2 ON S3 ON S4 ON S5 ON S6 OFF Ack Nak on S7 ON S8 OFF 19 200 Baud Rate RS 485 N 485 PCI 2 N 485 HUB 2...

Страница 19: ...pe Drive DVD CD burner Network backup utility Microsoft Windows XP Pro Windows 2000 Pro Server SP4 Question Which video Capture Card can be used with the NStar software Honeywell Access Systems recommends the PB VC 15 or higher capture card Call Honey Access Systems for more details Question What localized language support does the NStar software offer The initial release of NStar will be availabl...

Страница 20: ...ww honey wellaccess com for further details and downloads Question How do I default the NS2 panel 1 Change all of the NS2 Panel DIP switches to OFF address Zero 2 Power down NS2 panel by removing backup battery then removing AC power for 10 seconds 3 Restore power to the NS2 Panel by reconnecting AC power then backup battery to reset the panel 4 Power down again by removing backup battery then rem...

Отзывы: