7-101004-01
9
Honeywell Access Systems
NS2 Configuration Guide
NSLAN1 Connection
One NSLAN1 for each NS2 panel, Maximum sixty-four IP connections.
NStar Server
100BaseT (CAT 5) 328 Ft. Max.
100BaseT (CAT 5) 328 Ft. Max.
100BaseT (CAT 5) 328 Ft. Max.
EG
NSLAN1 must be
programmed with a
static IP address
See NSLAN1 product
documentation for
programing instructions.
DIP Switch Settings
S1-S5: Panel Address
S6: OFF (RS-485 Disable)
S7: ON (57,600 Baud Rate)
S8-S10: OFF
HUB
It is recommended to earth ground
(EG) each NS2 enclosure individually.
EG
NIC
NS2
Panel
NSLAN1
installed
NS2
Panel
NSLAN1
installed