NS2 Configuration Guide
Honeywell Access Systems
4
7-101004-01
Enclosure Specifications
Communications & Wiring
NOTE:
The C-100-A1/A2 (RS-232 communication loop), M-200 (1,200 Baud rate dial up modem), M-300-LO/LA
(1,200 Baud Leased line modem), F210D (Fiber to RS-232) [Discontinued] and F290D (Fiber to RS-485)
[Discontinued] are not supported with the NS2 panel(s).
Mounting
One NS2 panel in a standard 19-inch, high density enclosure. Up to
eight NS2 panels in a single 19-inch rack mountable enclosure
Dimensions
Board
9-inch Length x 5.5-inch Wide x 1-inch High
Enclosure
12.5-inch Wide x 14.5-inch High x 3.5-inch Deep
Environmental
Temperature
35–110° F operational
Humidity
0–85% RHNC
Communication Type
Description
Maximum Panels
Maximum Distance
Feet / Meters
Direct to COM Port
CBL50, RS-232 Cable
9-pin to RJ-45
1
50
15.25
N-485-PCI-2
RS-485 9-pin to CPU
31
4K
1219.5
Network
NSLAN1
Cobox Unit (RS-232)
1 NS2 panel per NSLAN1
64 max IP connections per system
328
100
LANSRL100/N-485-PCI-2L
Ethernet to RS-485
31 NS2 panels per 485 interface
64 max IP connections per system
328/4K
100/1219.6
LANSRLU1/N-485-PCI-2L
Ethernet to RS-485
31 NS2 panels per 485 interface
64 max IP connections per system
328/4K
100/1219.6
Modems
M-9600-LA (LO)/N-485-PCI
Lease-line Modem to RS-485
31
NA/4K
NA/1219.6
SHM-B-ASYNC/N-485-PCI
Short-haul Modem to RS-485
31
5279.9/4K
1609.84/
1219.6
SHM-B-ASYNC/CBL50
Short-haul Modem to RS-232
1
5279.9/50
1609.84/
15.25
M-9600-2/N-485-HUB-2
Dial-up Modem to RS-485
31
NA/4K
NA/1219.6
M-56/N-485-HUB-2
Dial-up Modem to RS-485
31
NA/4K
NA/1219.6
Fiber
FC485
Fiber converter to RS-485
31
10K/4K
3049/
1219.6
Cable Specifications
Description
AWG
Maximum Distance
Feet / Meters
Readers
NC1861-BL
6 Conductor, Shielded
18
500
152.5
Alarm Input
NC1821-GR
Twisted Pair, Shielded
18
2K
609.8
Relay Outputs
NC1821-GR
Twisted Pair, Shielded
18
2K
609.8