background image

10

VEA Product Guide —

 P/N LS10215-000NF-E:A 07/24/2018

Handover:  

 Commissioning engineer, commissioner / AHJ and customer representative should be satisfied on all aspects of commissioning and 

agree that the commissioning has met the required codes and standards. The detector must be ready for day to day operation prior to hand over. To 
hand over the system to the client obtain the relevant signatures and ensure that all required documents are included.  

VEA-040-Axx Detector Configuration Record

Use the Xtralis VSC application to print a record of the detector’s configuration. Select the detector on the Xtralis VSC tree view at the left and 
choose the Print command on the File menu.

Hand Over Documents
Copy of this form
Configuration printout or record
(if done) Specific performance test report
Forms required for compliance with local codes and standards

Customer’s Signature

Date:

Commissioner’s Signature

Date:

Содержание Notifier VESDA-E VEA Series

Страница 1: ...nd electri cal connections This document contains generic product information and some sections may not comply with all local codes and standards In these cases the local codes and standards take precedence The information below was correct at the time of printing and may be out of date check with your local codes standards and listings for current restriction FCC Compliance Statement This equipme...

Страница 2: ...F NOTIFIER Intelligent VESDA E VEA 40 point with LEDs VEA 040 A10 NTF NOTIFIER Intelligent VESDA E VEA 40 point with 3 5 Display Compatibility with FACP VEA 040 Axx NTF is compatible with the following NOTIFIER FACPs NFS2 3030 NFS2 640 NFS 320 Installation VEA is an addressable Aspirating Smoke Detector ASD with 40 addressable microbore tubes VEA is configured as an ASD in a 5 address space provid...

Страница 3: ...respective terminals on the SLC terminal block as shown in figure below Refer to the diagram below to wire the SLC detector to the FACP Communication ports All of the standard ports of VEA 040 Axx are available except for VESDAnet VESDAnet is not available to the user in these models of the detec tors However Gateway function is still applicable to this detector model to connect to Xtralis VSC SLC...

Страница 4: ...aded with Xtralis VSC software is directly connected to the detector using the USB port for initial configuration of the detector FACP Programing For FACP programing use the FlashScan ID FAASTX and Type Code ASPIRATION or ASPIR SUP Do not use ASPIR PRE ASPIR NON and ASPIR REF For the 40 addressable tubes use the FlashScan ID PHOTO and Type Code Smoke Photo SLC Address Assignment The SLC addressing...

Страница 5: ...air flow normalization process for the selected detector The normalization process determines the reference flow rate Normalization should be performed after changing pipe or monitoring pump settings The process takes approximately 30 minutes The detector must have been powered up for 5 minutes before the Normalization process can be initiated The detector can be in normal or disabled mode The pum...

Страница 6: ...cal Smoke Test command to complete the test Stop Local Smoke Test End an in progress local smoke test Fault 826 will cleared Start Leak Test Test for air leaks within the detector Test is performed automatically every 24 hours at a specified time Can be manually initiated from within the Xtralis VSC software Generates Fault 829 if leaks are detected Stop Leak Test End an in progress leak test Samp...

Страница 7: ...mulate full scale smoke level and initiates all alarm activity Alarm relays will energize unless the detector is disabled Procedure 1 Initiate the Start Alarm Test command from the Device menu 2 Select the tubes to be tested by editing the check boxes in the Enable column 3 Set the test duration default 30 seconds 4 Select Start 5 End the test early by selecting Stop Start Air Flow Fault Test Test...

Страница 8: ... Axx product guide can be set using the VSC software Follow the VEA 040 Axx product guide for information on setting up the remaining parameters GPIs and Relays General purpose inputs are not available to be configured via VSC Relay options are not available to be configured via VSC The following screen shot shows relay assignments for the SLC instance Tube Flow Scan The Tube Flow Scan function al...

Страница 9: ...mapped to the following categories at the FACP Use the Xtralis VSC software to further investigate the following faults Sensor fault Aspirator fault Communication fault Configuration fault Low flow fault High flow fault Filter fault clogged Low voltage fault Refer to the troubleshooting section of VEA 040 Axx product guide for additional fault information Commissioning Forms Customer Name Site Add...

Страница 10: ...o the client obtain the relevant signatures and ensure that all required documents are included VEA 040 Axx Detector Configuration Record Use the Xtralis VSC application to print a record of the detector s configuration Select the detector on the Xtralis VSC tree view at the left and choose the Print command on the File menu Hand Over Documents Copy of this form Configuration printout or record if...

Отзывы: