LCD2-80 Instruction Manual —
P/N 53242:B5 07/26/2019
15
Programming
ACS Mode Configuration
3.3.1 General Tab
Host Panel:
Node ID - Node ID of the host panel.
Panel Type - Select the host panel type from the drop-down menu.
ACS Addresses:
Start - Select the first annunciator address to be programmed.
End - Select the last annunciator address to be programmed.
Settings:
European Mode - Set European Mode to ON to have the word “fault” appear in the display.
Point Label Display Mode -
40 Characters: Select to display the 40 character point label in the second and third rows of the display for the first point/event that is
active. (Pressing the Step Display key will scroll through any other active events.)
20 Characters: Select to display two 20 character point labels in the second and third rows of the display for the first and last point/events
that are active.
Starting ACS Circuit Type -
SYS: The first eight points will be system points and are not programmable.
ACS: The full range of points are available for point programming.
System Trouble/Display Option - Set ON to have a general alarm or trouble message display in the system if there is no annunciator
point mapped to the device.
ACS Circuit Size - 64 or 96 points.
System Messages -
Description: Fixed message titles. The message associated with the description will display on the LCD2-80 when called for by a panel
command.
Message: These fields are populated with default messages that may be changed by the programmer.
Figure 3.3 General Tab
Содержание Notifier LCD2-80
Страница 20: ...20 LCD2 80 Instruction Manual P N 53242 B5 07 26 2019 Notes ...
Страница 21: ...LCD2 80 Instruction Manual P N 53242 B5 07 26 2019 21 Notes ...
Страница 22: ...22 LCD2 80 Instruction Manual P N 53242 B5 07 26 2019 EIA 485 Shield Terminations ...
Страница 24: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...