6
LCD2-80 Instruction Manual —
P/N 53242:B5 07/26/2019
Section 1: Product Overview
The LCD2-80 alphanumeric display module is an ancillary device used by Notifier fire alarm control panels including NCA-2, NFS-320,
NFS2-640, and NFS2-3030. The product operates in Terminal mode, where it acts as a display interface and mimics the host control
panel, or in ACS mode, where it can display custom messages.
1.1 UL 864 9th and 10th Edition
•
Per the UL Continuing Certification Program, UL 864 9th edition fire alarm control equipment will retain certification after the
rollout of UL 10th edition (12/2/2018).
•
approved by the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory.
http://iq.ulprospector.com
1.1.1 Products Subject to AHJ Approval
The following products have not received UL 864 9th or 10th Edition certification and may only be used in retrofit applications. Opera-
tion of the LCD2-80 with products not tested for UL864 9th or 10th Edition has not been evaluated and may not comply with NFPA 72
and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
1.1.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below must be approved by the local AHJ.
1.2 Features
•
80-character backlit LCD display.
•
Control switches for Acknowledge, Signal Silence, Drill System Reset, and Step Display/Lamp Test.
•
ABF-1/B package with key switch option.
•
Local piezo sounder with alarm/trouble resound.
•
EIA-485 connects to control panel terminal port.
•
In Terminal Mode:
• The LCD2-80 is a simplified version of the display for NCA-2, NFS-320, NFS2-640, and NFS2-3030.
• Mounts up to 6000 foot segments between units.
• Up to 32 of these terminals can provide annunciation and control from remote locations.
• Device type identifiers from control panel.
• Device and zone custom labels from control panel.
• Device address from control panel.
• EIA-485 connects to control panel terminal port.
• No programming necessary — mimics the host control panel.
•
In ACS Mode:
• The LCD2-80 supplies a means to display a subset of the panel message text, or to display custom messages programmed using
VeriFire® Tools.
• The power-limited EIA-485 interface provided by the control panel will support the installation of devices at up to 32 addresses.
• Zone/point message display programming done in VeriFire® Tools.
• European Mode display option (“Trouble” is called “Fault”).
NOTE:
The LCD2-80 should not be used as a primary display in Canada.
NOTE:
The LCD2-80 should not be used as a primary display for releasing service.
•
NCA
•
AFP-200
•
NFS-640
•
AFP-1010
•
NFS-3030
•
AM-2020
•
AFP-300/400
•
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated
below.
Program feature or option
Permitted in UL 864
(Y/N)
Possible settings
Settings permitted
in UL 864
Piezo Enable/Disable
N
SW3-2 ON = Piezo Disabled
SW3-2 OFF =Piezo Enabled
SW3-2 OFF =Piezo Enabled
Table 1.1
Содержание Notifier LCD2-80
Страница 20: ...20 LCD2 80 Instruction Manual P N 53242 B5 07 26 2019 Notes ...
Страница 21: ...LCD2 80 Instruction Manual P N 53242 B5 07 26 2019 21 Notes ...
Страница 22: ...22 LCD2 80 Instruction Manual P N 53242 B5 07 26 2019 EIA 485 Shield Terminations ...
Страница 24: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...