IDR-M Mimic Installation & Commissioning Manual
Appendix 1 - Specification
A1 - 1
997-412-000-3, Issue 3
June 2005
Appendix 1 - Specification
Mechanical
Construction:
Printed Circuit Boards (PCB) mounted
on metal chassis, designed for
mounting in an enclosure.
Note:
The mimic should be mounted
in a suitable enclosure. The enclosure
must conform to Panel Sealing
requirement: IP30, (EN-60529).
Dimensions:
Control or Driver PCB on bracket (mm):
126(w) x 240(d) x 45(h) approx.
Mimic Termination PCB on bracket (mm):
57(w) x 203(d) x 45(h) approx.
Fixing:
M4 (or equivalent) screw
Terminals:
External connections made using
screw terminals capable of accepting
cable sizes between 0.5mm
2
and 2.5mm
2
Environmental:
Climatic classification:
3K5, (IEC 721-2-3)
Operating temperature:
-5° C to +45° C, (recom5° C
to 35° C)
Humidity:
5% to 95% R.H.
Height above sea level:
Maximum, 2000m
EMC:
Emissions:
EN 61000-6-3
Immunity:
EN 50130-4
Safety:
EN 60950
Electrical
Operating Voltage:
18-32V*
Operating Current:
Control Board: 90mA
Driver Board:
Each Board -
10mA
Each LED
-
4.4mA
Max. total (Board & 64 LEDs) 265mA
Each relay
-
80mA**
Fuses:
Control Board:
Resettable thermal fuse. Nominal -
250mA; absolute max. - 600mA
Driver Board
0.5A(T), 20mm
Comms. Medium:
RS485 2-wire serial link
Isolation:
Functional at 42V
Baud Rate:
1200 Baud
Max. RS485 Network
Cable Length:
3000m (minimum of 1mm
2
screened
cable recommended)
* This may be limited by the requirements of any relays that
are driven from this supply. The minimum supply voltage =
the minimum relay pull-in voltage at the highest allowable
ambient temperature.
** This is the maximum allowable current per relay, which is
limited by the sink capabilities of devices on the board.