IDR-M Mimic Installation & Commissioning Manual
Installation Guide
12
997-412-000-3, Issue 3
June 2005
2.5.1.2 Control Board
The connections to this board are shown below.
Switch Configuration - RS485 Connection
Set the switches (located at position A):
a. Switches 1 to 6 set the IDR-M mimic
address, in the range 1 to 31 in binary (see
decode at left; switch 6 is always set to 0).
If all these switches are set to 0, there are
two possible conditions:
i
A soft address can be set by the IDR
Configuration Tool. See the instructions
supplied with the Tool.
ii
If no soft address is set, the hard address
is 0 (‘listen only’) which must only be used
during commissioning.
Note:
If used with an ID50 panel, only
addresses 1 to 16 are valid.
b. Switch 7 must be set according to the type
of connection used by the
mimic
, in this
case 0 for RS485 (does not have to be the
same as in (c) below).
c. Set switch 8 according to the type of
network used by the
fire panel
; set to 0 if
an RS485 network (i.e. Master/Slave) is
used, or to 1 if an ID
2
net network is used.
Ensure that the IDR-Mimic
does not share an address
with a repeater, and that the
address matches that
configured in the fire control
panel
Address
Switch settings (1=on)
1
2
3
4
5
6
1
1
0
0
0
0
0
2
0
1
0
0
0
0
3
1
1
0
0
0
0
4
0
0
1
0
0
0
5
1
0
1
0
0
0
6
0
1
1
0
0
0
7
1
1
1
0
0
0
8
0
0
0
1
0
0
9
1
0
0
1
0
0
10
0
1
0
1
0
0
11
1
1
0
1
0
0
12
0
0
1
1
0
0
13
1
0
1
1
0
0
14
0
1
1
1
0
0
15
1
1
1
1
0
0
16
0
0
0
0
1
0
17
1
0
0
0
1
0
18
0
1
0
0
1
0
19
1
1
0
0
1
0
20
0
0
1
0
1
0
21
1
0
1
0
1
0
22
0
1
1
0
1
0
23
1
1
1
0
1
0
24
0
0
0
1
1
0
25
1
0
0
1
1
0
26
0
1
0
1
1
0
27
1
1
0
1
1
0
28
0
0
1
1
1
0
29
1
0
1
1
1
0
30
0
1
1
1
1
0
31
1
1
1
1
1
0
Connection
to Termination
board
Connection to Mimic
Driver board
(SPI Bus)
A
B
No
connection
C
Processor reset
switch
No
connection
No
connection
No
connection
No
connection
No
connection
No
connection
No
connection
No
connection
Termination
Resistance
Termination
Resistance
IDR-M MIMIC
IDR-M MIMIC
IDR-M MIMIC
IDR-M MIMIC
IDR-M MIMIC
IDR-M MIMIC
FIRE CONTROL PANEL
FIRE CONTROL PANEL
EXAMPLE MASTER/SLAVE NETWORK CONFIGURATION
EXAMPLE MASTER/SLAVE NETWORK CONFIGURATION
0V
0V
0V
0V
B
A
24V
24V
24V
24V
B
A
B
A
AUX 24V
AUX 24V
B
B
A
IN OUT
A
Termination
Resistance
Termination
Resistance