PAGINA - 38
Installation and programming manual
AM-1224
NOTIFIER ITALIA
Doc. M-124.1-AM1224-ENG Rev A.1
AM-1224_manu
Example 1
: if the equation of the output 10 is DEL(00.30 01.30(L21)) then:
- After 30 seconds from the activation of the L21 line, the output 10 will be activated and will remain active for 1
minute and 30 seconds.
Example 2
: if the equation of the output 10 is DEL (00.30 00.40 (AND(L01 L04)))
- After 30 seconds from the alarm of the line L01 and L04, the output 10 will be activated and will remain
active for 40 seconds.
NOTE
if the delay introduced is = 00.00, the equation results active as became active the equation of delay
start and remains active for the time fixed in the lenght.
for every equation it is possible to have only one DEL user
if is not specified the lenght time in the Del equation, it will remain activated up to the reset of the
elemts indicated in the equation.
the maximum lenght time is 10 minutes.
the maximum delay time is 10 minutes.
SDEL
The operator "SDED" equals operator "DEL", except that if during the delay time the equation is no longer true,
the timer continues to count and then activate the output device.
To restore the timing it is necessary carry out a reset alarm.
Enter a space
character
Содержание Notifier AM12-24
Страница 1: ... AM12 24 Conventional fire panel ...