AM-1224
Installation and programming manual
PAGINA -
3
AM-1224_manu
Doc. M-124.1-AM1224-ENG Rev A.1
NOTIFIER ITALIA
E
E
L
L
E
E
C
C
T
T
R
R
I
I
C
C
A
A
L
L
F
F
E
E
A
A
T
T
U
U
R
R
E
E
S
S
Working temperature: -5°C
+40°C.
Relative Humidity: 10%
93% (no condensation).
Storage temperature: -10°C
+50°C.
Weigth:
4,7Kg
P
P
o
o
w
w
e
e
r
r
s
s
u
u
p
p
p
p
l
l
y
y
The internal power supply provide:
27,6 Vdc + 2 % - 10 %, 1,4 Adc with max. ripple 300 mV (summing panel power supply and outputs)
27,6 Vdc / 1A Battery charger.
B
B
a
a
t
t
t
t
e
e
r
r
y
y
C
C
h
h
a
a
r
r
g
g
e
e
r
r
s
s
e
e
c
c
t
t
i
i
o
o
n
n
Output Voltage = 27,5V.
Output Current= 1A ~ 100 mVpp max (with temperature compensation).
Batteries = 2 x 12V - 7Ah.
Suggested Batteries :
Yuasa type NP7-12 o NP7-12FR
(UL94) Faston - Capacity (20 Hr) = 12 V 7Ah
Dimensions = 151(b) x 65 (p) x 98 (h).
Fiamm type FG20721 o FGV20721
(UL94) Faston - Capacity (20hr) = 12 V 7.2Ah
Dimensions = 151(b) x 65 (p) x 98 (h).
Yuasa type NP18-12B o NP7-12BFR
(UL94) Screw - Capacity (20hr) = 12 V 17,2Ah
Dimensions = 181(b) x 77 (p) x 98 (h).
Fiamm type FG21803 o FGV21803
(UL94) Screw - Capacity (20hr) = 12 V 18 Ah
Dimensions = 181(b) x 77 (p) x 167 (h).
The followings are thresholds for faults indication on the Battery charger section:
Battery exaust = 21,5 Vdc.
Difference between batteries thresholds = 3,4Vdc
Battery cut-out thresholds = 20Vdc.
Current from battery in standby condition without mains (no 230 Vac): 180 mA (12 lines with End of Line
resistor – no external loads – display OFF)
Current from battery in Alarm condition without mains (no 230 Vac) : 320mA
G
G
r
r
o
o
u
u
n
n
d
d
Gound connection must be wired following CEI and ISPELS rules (Italy) or equivalent for different country.
In any case must ground circuit must have a resistance less than 10Ohm (measured at drain-well with
equipment disconnected). The Earth connection on CNAL terminals is mandatory .
P
P
a
a
n
n
e
e
l
l
M
M
a
a
i
i
n
n
s
s
C
C
o
o
n
n
n
n
e
e
c
c
t
t
i
i
o
o
n
n
This panel must be supplied with mains . In case of Mains loss the panel can continue to be supplied by internal
batteries for some time. Mains line required characteristics are:
Voltage : 230 Vac mono-phase + 10%
- 15%.
Frequency: 50 / 60 Hz.
Current from Mains: 0.45 Aac.
Note: Pay particular attention to don’t install the panel near high power
electromagnetic sources as Radio transmitters , electric motors and so on.