PAGE - 29 

AM8000_manu-inst 

  Doc. 160.1-AM8000-ITA Rev A.3 

NOTIFIER ITALIA 

POWER SUPPLY – Current calculation

 

The power supply must be able to continuously power all the internal system devices (and all external devices) 
during the stand-by period, that is in NON-alarm conditions. 

Use the table A to calculate the load in stand-by conditions. 

Use the table B to calculate the additional current which is  necessary in Alarm conditions  

A 24 Vcc internal power supply for a total of 4 Ampere is available on the power supply for the system operation 

 

 

  

NORMALcondition 

ALARM 

condition 

  

Item 

Current each 

Total Current 

(dev x Q) 

Current each 

Total Current 

(dev x Q) 

AM-8000 

 

 

 

 

CPU- 8000 

 

115 mA 

135 mA 

LIB-8000 

 

80 mA 

 

90 mA 

 

CAN-LCD-8000 

 

25 mA 

25 mA 

LCD-8000-L 

 

125 mA 

230 mA 

LCD-8000-F

 

 

165 mA 

270 mA 

Devices connected to Sounder 
Output 

 

1

 

 0

0

|_________| 

|_________|

Loops 

2

 Current 

Refer to 

Table 2

 

 

 

 

 

Loop 1 

 |_________|

 |_________|

Loop 2 

 |_________|

 |_________|

Loop 3 

 |_________|

 |_________|

Loop 4 

 |_________|

 |_________|

User Output current 

3

 

(Max 1.5A ) 

(Max 1.5A) 

LCD-6000  

 

Bells  

0

|_________|

 

|_________|

Sounders 0 

0

|_________|

 

|_________|

Strobes 0 

0

|_________|

 

|_________|

Other devices 

|_________|

 

|_________|

|_________|

 

|_________|

 

 

 

 

 

 

Total 

4

 = 

 

Total    = 

 

 

 

 

  (x24h) or (x72h) = 

 

x 0.5 h  = 

 

 

Stand-by (A) 

Ah

Alarm  (B) 

Ah

 
 
 
 

 

Ah Battery = (A + B) x 1.2 

5

 = 

Ah

 

1  Check the load for each  output is within admitted limits  

 

2  

Current from loops

Refer to the device manufacturer data sheet for the current necessary in normal mode. 

    Calculate the total current required for each loop by using the 

table 2 (refer to the following).  

    

Alarm current

: Refer to the devices manufacturer’ data sheet for the current necessary in alarm mode. 

    Calculate the total current required for each loop by using the 

table 2 (refer to the following) 

taking into account that the control unit controls 

the activation 

only of the first 

6 sensor and input module LED in alarm 

Check that the 

total current for each loop is lower than 500 mA

 

3  Refer to the device manufacturer data sheet for the current necessary in normal and alarm mode. Check that 

the total current is lower than 

1,5 

Ampere. 

 

4  The current request for the stand-by or alarm conditions cannot, in any case, exceed the power supply capacity. If the calculated current 

exceeds the value of 4 Ampere, available at the power supply, the exceeding current, necessary during the Alarm condition, is drawn from the 
batteries. 
 

5 The sum of currents obtained must be multiplied by a 1,2 factor to take account of the battery  manufacturing tolerances. 

                                                      
 

 

Содержание NOTIFIER AM-8000

Страница 1: ...AM 8000 Intelligent Addressable Fire detection P l Installation manual ...

Страница 2: ......

Страница 3: ...tputs 10 Sounder Output 11 System Components 12 Black Box 12 AM 8000 CPU card 12 CNU CNU terminal block 13 DIP SWITCH on CPU CARD 14 AM 8000 Front Panel LCD 14 DIP SWITCH on LCD CARD 16 LCD 8000 installation 16 CAN LCD 8000 card 17 System Wiring 19 System Wiring example 21 CAN Bus Wiring Cables 22 LIB 8000 card 23 LIB 8000 CNU terminal Block 23 Communication lines with Detectors Modules 24 Technic...

Страница 4: ...lease consult NOTIFIER Technical Service for any doubt This system like all solid state components may be damaged by induced electrostatic voltages handles the boards keeping them among the edges and avoid to touch the electronic components An appropriate earthing connection ensures in any case a sensitivity reduction to disturbances Please consult NOTIFIER Technical Service if you cannot solve in...

Страница 5: ...control unit is in conformity with the following EN54 4 requirements Function EN 54 4 reference Power supply from main source Power supply from battery source in standby Re charging and check of the battery source Power supply fault detection and signalling 5 1 5 2 5 3 5 4 EN54 EN54 2 13 7 Max 512 Sensors Manual Call Points per microprocessor The AM 8000 control unit has a maximum capacity of 636 ...

Страница 6: ...rnal loads such as sirens bells etc OUTPUTS 1 Supervised Siren Output 1 General Alarm Output with contacts free from voltage 1 General Fault Output with contacts free from voltage Mechanics The control unit mechanics is suitable for wall installations Sizes 403mm L x 408mm H x 240mm P Protection grade IP 30 Operation temperature 5 C a 40 C Stockage temperature 10 C a 50 C Weight 7 5 Kg Main Functi...

Страница 7: ...ats masonry walls or self tapping screws pre fabricated panels It is recommended not to install the panel near heat sources radiators etc Use screws of max 5 mm The control unit must be installed to the wall so as to allow a clear view of the display and easy access by the operator For example it allows an optimal view of the display at 1 5 m height It is recommended not to install the control uni...

Страница 8: ...e PAGE 5 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA Extractable labels on the front panel AM 8000 control unit is provided with extractable labels to indicate the functions Status via LED and some function buttons ...

Страница 9: ... 9Vdc 4 A ripple max 500mVpp Power supply for control unit user output external load power supply Battery charger section Output voltage 27 5 Vdc 500mA Vpp max temperature compensation Output current 1 5A ca Number of batteries that can be connected 2 x 12 V min 7Ah max 27Ah max The battery charger section has the following signalling thresholds Exhausted battery threshold 21 5 Vdc Re charge Fault...

Страница 10: ...tery breakdown will be indicated when their voltage is 21 5V and to prevent irreversible damages the voltage will be automatically switched off by disconnecting the batteries when the voltage is 19 5V All wirings MUST be checked BEFORE they are connected to the control unit It is recommended to perform at least the following checks Check the continuity of all cables used including the shield Ensur...

Страница 11: ...ty class The mains supply conductors shall not be consolidated by means of a soft welding A sectioning device external to the control unit must be provided for the 230 Vac power cable contact separation 3 mm min The sectioning device must be omni polar or must disconnect the line phase Power Supply connection must be done following this procedure Refer to Base Board 1 Turn off the main power switc...

Страница 12: ...108mA LCD not connected 1x LIB 8000 at nominal voltage 24Vdc 75mA LCD 8000 L at nominal voltage 24Vdc and full backlight 169mA if the LCD is connected to the CPU 8000 Card 218mA if LCD have remote connection by CAN LCD 8000 adaptor LCD 8000 F at nominal voltage 24Vdc and full backlight 215mA if the LCD is connected to the CPU 8000 Card 274mA if LCD have remote connection by CAN LCD 8000 adaptor ex...

Страница 13: ...d USR2 The USR1 and USR2 relays are available in free voltage contacts NOTE do not connect to this output any alarm remote control such as a telephone dial EN 54 2 7 7 because the output line is not controlled Contact range max 30 VAC DC 2A Non inductive loads Selection of type of contact Normally open or Normally closed through JURS1 e JUSR2 Jumpers on board refer to basic board topography NOTE T...

Страница 14: ...line ATTENTION Polarity displayed are in Alarm condition at idle condition they are inverted Sounder connection controlled output Polarized devices electronic sirens etc 47 K W 3 4 Non polarized devices Bells relays etc 47 K W 2 x 1N 4004 3 4 Sounder output operation window CNU 4 3 Siren output connections refer to basic board topography IDLE CUT SHORTCIRCUIT 21K 61K ...

Страница 15: ...u inst SYSTEM COMPONENTS Black Box Each Black Box is equipped of one CPU card and can contain up to 2 Loop Interface cards LIB 8000 Each LIB card can drive up to 2 ADV loop Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol or 99 99 in CLIP mode AM 8000 CPU card ...

Страница 16: ...ommunication line side A for AUDIO CAN bus devices AUDIO 1 Line Can Bus with internal EOL resistor Power Supply line is protected with a 4 Fuse 19 General Fault NO NC 20 General Fault C General Fault Relay Contacts 2A 30V Normally Open or Closed selectable via JGST Jumper 21 General Alarm NO NC 22 General Alarm C General Alarm Relay Contacts 2A 30V Normally Open or Closed selectable via JALL Jumpe...

Страница 17: ...ack Box n 6 ON ON ON off Black Box n 7 off off off ON off off off off Black Box n 8 Box ID proper configuration ON off off off Dip 5 ON from USB key loads configuration previously prepared by PK 8000 SW Tool Box ID proper configuration off ON off off Dip 6 ON copy the configuration in the USB memory key Box ID proper configuration off off off ON Dip 8 ON Use only by authorized Technician Note Set ...

Страница 18: ...0 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA NOTE The two CPU cards of the two available LCD models LCD 800 F and LCD 8000 L differs in the component and in the software but maintain all end user Connectors and Dip Switches in the same positions and with the same pin out ...

Страница 19: ...off LCD n 5 Normal Operation off ON ON off off LCD n 6 Normal Operation ON ON ON off off LCD n 7 Normal Operation off off off ON off off LCD n 8 Normal Operation ID proper configuration Off Off Off ON LCD n ID Use only under manufacturer autorization LCD 8000 L F installed in the Black Box front door To install the LCD on the Front Panel door Open the door Take off the plastic cover removing the f...

Страница 20: ...PAGE 17 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA LCD 8000 L F installed along the CAN Bus Network use CAN LCD 8000 CARD This card is necessary when the LCD is not installed in the same cabinet with the AM 8000 CPU ...

Страница 21: ...er min 18Vcc a max 40Vcc must be provided Operating Temperature 5 C a 40 C Humidity Max 95 no condensation Stockage temperature 10 C a 50 C Current consumption LCD 8000 L backlight low 148mA in Normal condition 218mA in alarm condition 24Vcc LCD 8000 F full backlight 236mA in Normal condition 274mA in alarm condition 24Vcc CAN LCD 8000 16mA 24Vcc CAN LCD 8000 card CNFR 10 pins connector to connect...

Страница 22: ...AM 8000 Manuale di installazione PAGE 19 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA ...

Страница 23: ...tion And also the Power supply connection MUST BE in the same configuration If this function is not appropriately followed it can contravene the EN54 requirements Here are some samples of the power supply and CAN bus wiring Note that Each LCD have TWO connections for the CAN Network Each LCD have TWO connections for the Power Supply CAN Bus IN OUT connections must be wired in separated path LCD Po...

Страница 24: ...AM 8000 Manuale di installazione PAGE 21 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA System Wiring Example ...

Страница 25: ...ngle pair for CAN Bus Belden 3105 A Twisted pair 22 AWG for Can Bus only Using this cable maximum distance from first to last equipment is 300 mt at maximum transmission speed of 31250 bit sec Power Supply Cable Power supply cable can be a twisted pair with copper section proportional to o the distance from first and last equipment o Number and current consumption of all devices along the line o m...

Страница 26: ...iption Characteristics Note 12 Fault relay Common 11 Fault relay N C N O Max 30V 1A Select N O N C with JGST Jumper 10 Alarm Relay Common 9 Alarm Relay N C N O Max 30V 1A Select N O N C with JALL Jumper 8 Line 2 B 7 Line 2 B 6 Line 2 A 5 Line 2 A Detection LINE 2 4 Line 1 B 3 Line 1 B 2 Line 1 A 1 Line 1 A Detection LINE 1 DIP SWITCH SW1 1 2 3 4 LIB1 ON OFF OFF OFF LIB2 OFF ON OFF OFF ...

Страница 27: ...f analogue line connection cables Type of cable 2 conductors for their section refer to the table below Twisted narrow pitch 5 10 cm Shielded pair cable Max admitted capacity 0 5 uF Cable section The sections are referred to the total length of the line in case of STYLE 6 loop and therefore when the loop is closed it is considered the loop length which however must not be longer than 3000 meters a...

Страница 28: ...the specific device connections please refer to Analogue system device installation manual document M 199 1 SCH ITA or M 199 1 SCH ENG by Notifier Italia Example of closed line style 6 or Loop The total length of the loop couple from the Panel Loop output and input SHALL NOT exceed 3 000 mt MCP M700KI A SIDE B SIDE MCP M700KI MCP M700KI ...

Страница 29: ... line Place a test prod of the tester on the line cable screen and the other test prod on the positive cable of the same line The resistance measured must be higher than 15 20 MOhm better if infinitive Perform the same operation between the line screen and negative cable Check that also in this case the resistance is higher than 15 20 MOhm Earthing lines insulation Place a test prod of the tester ...

Страница 30: ...ing connection is compulsory and must be fixed to the cabinet by means of a cable fixing device so that it cannot be accidentally stripped off The power supply connection must be performed through the following phases refer to basic board topography Turn off the main switch of the 230 Vca mains which powers the control unit Disconnect the CNAL terminal block from the control unit Connect the 230 V...

Страница 31: ... off General Fault relay deactivated 3 Disconnect both batteries wait not more than 2 3 minutes for the control unit to signal The indication of BATTERIES NOT CONNECTED on the display Yellow led FAULTS flashing Yellow led POWER OK on Yellow led MAINS on General Fault relay active Re connect the batteries and press the SILENCE ALARM FAULT key and check No breakdown signalling on the display Yellow ...

Страница 32: ..._________ Other devices _________ _________ _________ _________ Total 4 Total x24h or x72h x 0 5 h Stand by A Ah Alarm B Ah Ah Battery A B x 1 2 5 Ah 1 Check the load for each output is within admitted limits 2 Current from loops Refer to the device manufacturer data sheet for the current necessary in normal mode Calculate the total current required for each loop by using the table 2 refer to the ...

Страница 33: ...e Modules serie 700 Double Modules serie 700 Modules serie MA MMX 10 N CMX 10 R Isolation modules Addressable Sounders Power from loop Other devices N B Total must be less than 0 500 A Total loop N 2 Total loop N 2 Detectors serie NFX Detectors serie 700 MCP Single Modules serie 700 Double Modules serie 700 Modules serie MA MMX 10 N CMX 10 R Isolation modules Addressable Sounders Power from loop O...

Страница 34: ...CZ 288 μA 8 8mA External Power M710E CZ 1 5 mA 8 8mA Loop Power M710E CZR 500 μA 8 8 mA External Power M710E CZR 6 5 mA 8 8 mA Loop Power ZMX 1E 200 μA 9 mA External Power IMX 1 200 μA 4 mA M710 E 310 μA 5 mA MMA1 I 400 μA 5 mA MCX 3 450 μA 5 mA M701E 310 μA 5 mA CMA1 I 410 μA 5 mA M500KA 200 μA 5 mA M700K 260 μA 5 mA M700KI 360 μA 5 mA NBG 12LX 100 μA 5 mA P700 390 μA 5 mA M720 340 μA 5 mA M721 3...

Страница 35: ...e Via Telesio 15 Tel 055 696706 Fax 055 6529294 00118 Roma Via Del Casale Santarelli 51 Tel 06 7988021 Fax 06 79880250 E mail notifier roma notifier it 80143 Napoli Via G Porzio 4 Centro Direzionale Isola E2 Scala B Piano 5 int 19 Tel 081 7879398 Fax 081 7879159 E mail notifier napoli notifier it 70125 Bari Via Della Costituente 29 Tel 080 5013247 Fax 080 5648114 E mail notifier bari notifier it 9...

Отзывы: