PAGE - 10
Manuale di installazione
AM-8000
NOTIFIER ITALIA
Doc. 160.1-AM8000-ITA Rev A.3
AM8000_manu-inst
Relay outputs
EN54
!
EN54-2 8.8
General Fault Output
The General Fault relay is usually in energized state. It is de-energized in Fault
condition.
NOTE:
do not connect to this output any alarm remote control, such as a
telephone dial (EN 54.2. 7.7) because the output line is not controlled
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JGST Jumper on
board (refer to basic board topography)
EN54
!
EN54-2 7.7
General Alarm Output
The main Alarm relay is available in free voltage contacts
NOTE:
do not connect to this output any alarm remote control, such as a telephone
dial (EN 54. 2. 7.7) because the output line is not controlled.
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JALL Jumper on board
(refer to basic board topography)
CNU
NC/ NO COM
21 22
EN54
!
EN54-2 7.7
Outputs
USR1and USR2
The USR1 and USR2 relays are available in free voltage contacts
NOTE:
do not connect to this output any alarm remote control, such as a telephone
dial (EN 54. 2. 7.7) because the output line is not controlled.
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JURS1 e JUSR2
Jumpers on board (refer to basic board
topography)
NOTE:
To program the activation of these outputs refer
to “Am-8000 Programming Manual”
CNU
USR1
NC/ NO COM
23 24
CNU
USR2
NC/ NO COM
25 26
FUNCTION
Siren
General Alarm
General Fault
USR1
USR2
CHARACTERISTICS
1 contact controlled by
24Vcc / 2A resistive
Max 2A resistive 30 Vdc, NA-NC
selectable through Jumper JALL
(
refer to basic board topography
)
Max 2A resistive 30 Vdc, NA-NC
selectable through Jumper
JGST
(
refer to basic board topography
)
Max 2A resistive 30 Vdc, NA-NC
selectable through Jumper
JUSR1
(
refer to basic board topography
)
Max 2A resistive 30 Vdc, NA-NC
selectable through Jumper
JUSR2
(
refer to basic board topography
)
Main Fault output connections
(refer to basic board topography)
CNU
NC/ NO COM
19 20
Main Alarm output connections
(refer to basic board topography)
URS1 e USR2 output connections
(refer to basic board topography)