AM-8000
Manuale di installazione
PAGE - 13
AM8000_manu-inst
Doc. 160.1-AM8000-ITA Rev A.3
NOTIFIER ITALIA
CNA
terminal block
N°
description
Function
Note
1
Phase
2
Eatrh
3
Neutral
230Vac mains Power
Fused with 3,15 AL
CNU
terminal block
N°
Name
description
Note
1
+24V USR
2
GND USR
Fused with 4 A fuse
3
Sounder/ Siren (positive in
non alarm)
4
Sounder/ Siren (Negative in
non alarm)
Fused with 1,35A resettable fuse (this is a
(polarity inversion output
).
EOL resistor = 47K
Ω
5
Not used
6
LIN +
7
GNDIS
8
LIN -
RS.485 Opto-insulated
NO EOL Internal resistor
9
VPPLA
10 GNDP
POWER supply line
for LCD CAN bus devices
11 CDAHA
12 GND
13 CDALA
Communication line (side A)
for CAN BUS NETWORK
Can-Bus (Output Line)
with internal EOL resistor
Power Supply line is
protected with a 4° Fuse
14 VPPL1
15 GND1
POWER supply line
for CAN bus AUDIO devices
16 CAN
H1
17 GND
18 CAH
L1
Communication line (side A)
for AUDIO CAN bus devices
AUDIO 1 Line
Can-Bus with internal EOL
resistor
Power Supply line is
protected with a 4° Fuse
19
General Fault : NO-NC
20
General Fault : C
General Fault Relay
Contacts
:
2A 30V
Normally-Open or Closed
selectable via JGST Jumper
21
General Alarm : NO-NC
22
General Alarm : C
General Alarm Relay
Contacts
:
2A 30V
Normally-Open or Closed
selectable via JALL Jumper
23
User1 : NO-NC
24
User1 : C
User 1 Relay
Contacts
:
2A 30V
Normally-Open or Closed
selectable via JUSR1
25
User2 : NO-NC
26
User2 : C
User 2 Relay
Contacts
:
2A 30V
Normally-Open or Closed
selectable via JUSR2
27 VPPLB
28 GNDP
POWER supply line
for CAN bus LCD devices
29 CDAHB
30 GND
31 CDALB
Communication line (side B)
for CAN BUS NETWORK
Can-Bus (Input Line)
with internal EOL resistor
Power Supply line is
protected with a 4° Fuse
32 VPPL2
33 GND1
POWER supply line
for AUDIO CAN bus devices
34 CAN
H2
35 GND
36 CAN
L2
Communication line (side A)
for AUDIO CAN bus 2
AUDIO 2 Line
Can-Bus with internal EOL
resistor
Power Supply line is
protected with a 4° Fuse