Programming the AM2020/AFP1010 for Remote Annunciation
D.4 Programming the AM2020/AFP1010 for Remote Annunciation
Annunciator points must be programmed from the AM2020/AFP1010 before the annunciators will function. To program the annunciators
into AM2020/AFP1010 memory, and to map system points and software zones to annunciator points, refer to the
AM2020/AFP1010 Man-
ual.
The AM2020/AFP1010 employ the following format for annunciator points:
D.5 Configuring Annunciators for AM2020/AFP1010
The switch numbers given below are for SW28 on the ACM-24AT and ACM-48A, and for the 8-pin DIP switch on the ACM-16AT and
ACM-32A. Address and DIP switches must be set before the annunciator will operate properly. See Section 5.2 for switch locations.
D.6 Configurations for Specific Applications
The ACS is a vital part of voice alarm applications with the AM2020/AFP1010. An ACM-24AT or ACM-16AT allows for manual selection
of speaker or telephone circuits and can provide common system annunciation of circuits and software zones. Dedicated annunciators are
required for each of the following specific types of applications:
•
Common System Annunciation
•
Speaker and Telephone Mode
•
Manual Override
D.6.1 Common System Annunciation
An ACM-24AT or ACM-16AT module may be used to annunciate AM2020/AFP1010 circuits and software zones. If located remotely and
used to execute control functions (Acknowledge, Signal Silence, Reset), the DIP switches on the annunciator must be set as follows. The
switch numbers given below are for SW28 on the ACM-24AT, and for the 8-pin DIP switch on the ACM-16AT and ACM-32A.
A(xx) P(yy)
Annunciator address
In the range of 1-32, as set on
the annunciator’s rotary decimal
switches.
Annunciator Points per Module
ACM-24AT,
Points 1-24
First
AEM-24AT,
Points 25-48
Second
AEM-24AT,
Points 49-64
Note:
Points 65-72
are not used
ACM-48A,
Points 1-48
AEM-48A
Points 49-64
Note:
Points 65-96 are not used
ACM-16AT,
Points 1-16
First
AEM-16AT,
Points 17-32
Second
AEM-16AT,
Points 33-48
Third AEM-16AT,
Points 49-64
ACM-32A,
Points 1-32
AEM-32A,
Points 33-64
NOTE:
When using the NCA to annunciate points on the AM2020/AFP1010 over the network, enable state reporting in the AM2020/AFP1010
panel for control module points and “NONA”/”NOA” module points; refer to the
NCA Manual
for instructions.
Switch #
ACM-24AT and ACM-48A
1
ACM-16AT and ACM-32A Function
1
Manual override: Set “ON” when the annunciator is used for manual override of control relays.
2, 3
Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 for ACM-
24AT/ACM-48A; see Section 5.13.3 for ACM-16AT/ACM-32A.
4
Not used; set to OFF
Eight-Point Shift: Set to “OFF”.
5
Receive Only: Set this switch “ON” for each annunciator that will provide the same information as another annunciator in a different location.
(When two or more annunciators hold the same address, all but one must be configured as “Receive Only” annunciators.)
6
Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is “ON”.)
7
Switch Inhibit: Set this switch “ON” to disable the point control switches on the annunciator and prevent them from executing system control
functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will
function only in a local capacity unrecognized by the system.
8
Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the
piezo from sounding.
1
See Sections 5.12.1 and 5.12.4 for details about SW32 on ACM-24AT and ACM-48A.
Switch #
ACM-24AT and ACM-48A
ACM-16AT and ACM-32A Function
1
Manual override: Set switch “OFF” for this application.
2, 3
Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3,
“Configuring Number of Expander Modules” for ACM-24AT/ACM-48A; see Section 5.13.3, “Configuring Number of Expander
Modules” for ACM-16AT/ACM-32A.
4
Not used; set to OFF
Eight-Point Shift: Set to “OFF”.