ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 20
997-291, Version 3.05
November 2010
3
Select Input Device Type. Zones only -
select whether the input device is of any
type or restricted. Zones and cells - select
the number of devices that must be in
coincident alarm (for zones, must be in the
same zone. For cells, may be in the same
cell or across a range, as set in
is no coincidence. Device coincidence is
not available for zones if zone coincidence
is already set.
Note:
If the ‘Any zone’ event is selected, then
for device coincidence to occur the
devices must either be in the same
panel (or network) or be in the same
zone, depending upon the ANY ZONE
panel setting (
Note:
The following ‘Input Device Type’
options are provided for use with the
Alarm input and the extinguishing
system output, but are available for any
Alarm input:
Smoke and Heat Sensor
Sensor and MCP
VIEW and Other Sensor
If any of these are chosen, Devices
Coincidence is not available.
‘Any Input device type’ includes Virtual Input
Points within the selected zone(s).
3
EN54-2: 7.1.4
CAUTION: Do not include
MCPs in a coincidence group.
To avoid configuring MCPs into the coincidence
group you must configure two separate Control
Matrix Rules:
i) The first should define the MCP Device Type (e.g.
Any Manual Call Point) without coincidence.
ii) The second should define an input Device Type
(e.g. Any Analogue Sensor) with coincidence.
The use of zone coincidence and
restricted-by-type in the same
Control Matrix entry is not
supported in the panel.