ID3000/ID2000 Fire Panel Configuration Tool Manual
Network
6 - 6
997-291, Version 3.05
November 2010
7
Select Report Fallback ‘No’ or ‘Yes’ (by
default, if the Master loses communication
with a Slave panel then any Control Matrix
Rules for which ‘Fallback Input’ is selected
[see
their input statement becomes true. To
prevent this for a specific Slave panel, select
‘No’ for that panel).
Note:
Station Names are configured
automatically from those entered on the
Specification Tab (
Master and each Slave.
Event Distribution (ID2000 Master/Slave only)
8
For each event that is transmitted on the
network, select (check box) which station(s)
it is sent to from the panel at which it occurs.
By default, all events are sent to all stations.
It is unlikely that this will need to be
changed
; if you do so, note:
a. Events sent from a Slave (to another or to a
repeater) have to be sent to the Master also.
b. Pushbutton events except Evacuate have
‘Conditional’ and ‘General’ options. If both
options are sent, the pushbutton has effect
regardless of the origin of any alarms or
faults. If only ‘Conditional’ is sent, the control
has an effect at the other panel only if the
the alarm or fault originated at the panel at
which the pushbutton was pressed and
there are no alarms or faults originating at
any other panel. It is not meaningful to send
only ‘General’.
7
EVENTS ARE NOT DISPLAYED UNTIL A MASTER-SLAVE
NETWORK IS CONFIGURED
8a-8f
8