
ID3000/ID2000 Fire Panel Configuration Tool Manual
Loop Devices
3 - 20
997-291, Version 3.05
November 2010
x
Logged/Not Logged
. For modules of type
AUX only, set individually as ‘logged’
(recommended for fire-critical equipment)
or ‘not-logged’ (overridden by panel ‘Log’
setting, see
information).
xi
Backup Alarm Monitor
(MON modules on
ID
2
net only): If device is intended to relay
alarm status from a neighbouring panel to
provide backup if the ID
2
net fails, select
this option to ensure that alarms are treated
correctly by the panel. Do not include the
device in zone-specific or device-specific
Control Matrix rules. Backup Alarm Monitor
cannot be set at the same time as
Technical Alarm Input.
xii
Technical Alarm
(Benelux Sprinkler Panel
only). If this option is selected,
the
sounders do not operate
. Instead, the
NON-FIRE ACTIVE LED illuminates on all
panels on the network. Relays and other
modules operate as in a fire condition. Only
effective if ‘Detect Fire’ supervision is set
to ON. Not available for modules of types
BELL, CTRL and AUX. ID3000: device is
displayed on Tech. Alarm tab instead of
Fire tab.
11
To exit, click OK.
11x
11xi
11ix
11
Benelux Sprinkler Panel: Technical
Alarm contravenes EN54-2: 5.6, 6
by lighting the zonal FIRE LED.