NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Program
Point Program
PREALARM:
Press this softkey to select
ALERT
or
ACTION
for the Prealarm function. Refer to
the section on Prealarm in Appendix D, “Intelligent Sensing Applications” for a description of
Alert and Action.
SILENCEABLE:
This field determines whether the user can manually silence a detector’s
activated sounder/relay base. Values are as follows:
INTELLIGENT SOUNDER:
Press this softkey to select
YES
if an Intelligent Sounder Base is
installed for this detector.
SOUNDER BASE SETUP:
Press this softkey to proceed to the Sounder Base Setup screen. This
option will only be available if the
INTELLIGENT SOUNDER
is set to
YES
.
CO PRE-ALARM:
Press this softkey to select
YES
or
NO
to enable the CO Prealarm function for
the PHOTO/CO smoke detector. This field is only available when programming the PHOTO/CO
smoke detector.
Sounder Base Setup
Figure 3.39 Sounder Base Setup Screen
Soft Keys
A U X T O N E 1 :
Press this softkey to select
C O N T I N U O U S
,
T E M P - 3
,
T E M P - 4
,
M A R C H
or
C U S T O M
for the first auxiliary tone of the intelligent sounder base.
A U X T O N E 1 C O N T R O L :
Press this softkey to enter the Logic, General or Trouble Zone that
will control the activation of the first auxiliary tone of the intelligent sounder base.
A U X T O N E 2 :
Press this softkey to select
C O N T I N U O U S
,
T E M P - 3
,
T E M P - 4
,
M A R C H
or
C U S T O M
for the second auxiliary tone of the intelligent sounder base.
A U X T O N E 2 C O N T R O L :
Press this softkey to enter the Logic, General or Trouble Zone that
will control the activation of the second auxiliary tone of the intelligent sounder base.
NO
Not manually silenceable
YES
-
RESOUND FIRE
Silenceable, resound on fire alarm events
Network and Local Resound
YES
-
RESOUND
SUPERV
Silenceable, resound on supervisory events Network and Local Resound
YES
-
NO
RESOUND
Silenceable, does not resound
NOTE:
In network applications, specific nodes can be excluded from having the ability to initiate a
resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the
VeriFire Tools
help file
.
S O U N D E R B A S E S E T U P
L 0 3 D 1 2 3
A U X T O N E 1 : T E M P - 3
A U X T O N E 1 C O N T R O L : Z L 0 0 4 0
A U X T O N E 2 : T E M P - 4
A U X T O N E 2 C O N T R O L : Z L O O 4 1 A C C E P T
V O L U M E : H I G H B A C K