150
NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Regional Settings
Chicago
I.2 Chicago
The
REGIONAL
SETTING
choice of
CHICAGO
disallows local drill or signal silence.
• The DRILL and SIGNAL SILENCE keys at the panel will not function.
• Annunciator Control Modules and SLC modules given a drill or signal silence Mode or
Type Code will not allow local drill or signal silence initiation.
• Events must be acknowledged prior to system reset.
I.3 Australia
The
REGIONAL
SETTING
choice of
AUSTRALIA
activates the following features:
• allows use of the Australian smoke control module SCS-8AU.
• “Brigade Act” LED is controlled by ZL1000.
• Test LED is lit during walktest.
• Ability to manually corrupt memory to test memory corruption detection. Special passwords
for testing memory corruption detection.
“corrupta” will temporarily corrupt a location in the application.
“corruptb” will temporarily corrupt a location in the boot.
“corruptd” will temporarily corrupt a location in the database.
“reset” will uncorrupt the panel and reboot.
• Plant Isolate button will disable/enable ZL999. Use special function zone ZF6 with ZL999.
• No softkeys on the panel will function while there is an unacknowledged alarm
EXCEPT
scroll, silence, reset and disable.
• Silence Buzzer key acknowledges everything before silencing.
• Special Function Zone ZF17 may be used with Signal Silence. When a Signal Silence is
performed, ZF17 will go active and remain active until a System Reset is performed.
• Disable key disables the current event on the screen.
• Special Function Zone ZF7 may be used for Drill. When the drill key is pushed or a drill
performed, ZF7 will go to active. When the system reset key is pushed or a system reset is
performed, ZF7 will go normal.
• Fan control function per AS/NZS 1668:1:1998, section 4.13.2.
• First zone in alarm displayed at top of display. Additional zones in alarm also displayed,
until panel reset. Alarm zones not currently on display may be viewed using the scroll
button.
• Security events will light the supervisory LED. The supervisory scroll key will scroll
through security events.
• Display acknowledged and unacknowledged alarms at the same priority.
• Pre-alarm events will be displayed after alarms.
• The Main Menu includes an “Other events” menu key to scroll through other events.
• Password Bypass Timer enabled. After entering a valid password, the user does not need to
enter a password again until no key is pressed for ten minutes.
• Active Output events are displayed if Output Activations are enabled in the Event Logging
menu.
• Disable/Enable button will disable or enable the currently-displayed event.
• AMPS-24 supervision disabled.
• When the primary supply is not an AMPS-24, selecting AUX trouble supervisory setting
will generate a general power supply fault.