NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Type Codes
Type Codes for Input Devices
PULL STATION
fire alarm
Y
Y
Manual fire-alarm-activating device
SMOKE CONVEN
fire alarm
Y
Y
Indicates activation of a conventional smoke detector. An FZM-1
must be used for alarm verification of a two-wire conventional
detector.
SMOKE DETECT
fire alarm
Y
Y
Indicates activation of a conventional smoke detector. An FZM-1
must be used for alarm verification of a two-wire conventional
detector
WATERFLOW
fire alarm
Y
Y
Monitor for waterflow alarm switch
WATERFLOW S
supervisory
Y
Y
Indicates supervisory condition for activated waterflow switch
ACCESS MONTR
non-alarm
security
N
Y
Used for monitoring building access
AREA MONITOR
security
Y
Y
Monitors building access
AUDIO SYSTEM
trouble
N
N
Used for monitoring audio equipment (use trouble zones for
activations)
EQUIP MONITR
non-alarm
security
N
Y
Used for monitoring equipment
FMM-420
user-
programmable
Y
Y
Monitors 4-20 mA industrial sensors.
SECURITY L
security
Y
Y
Indicates activation of security alarm
LATCH SUPERV
supervisory
Y
Y
Indicates latching supervisory condition
NC SUP L
supervisory
Y
Y
Indicates latching supervisory condition, where an open
circuit=active.
TRACK SUPERV
supervisory
N
Y
Monitors for waterflow tamper switches for alarm points
NC SUP T
supervisory
N
Y
Indicates tracking supervisory condition, where an open
circuit=active.
SPRINKLR SYS
supervisory
Y
Y
Monitors a waterflow device
SYS MONITOR
security
Y
Y
Monitors equipment security
TAMPER
supervisory
Y
Y
Indicates activation of tamper switch
ACK SWITCH
non-alarm
N
N
Performs Acknowledge function
ALLCALL PAGE
non-alarm
N
Y
Performs function AMG-1 All-call and telephone page
DRILL SWITCH
non-alarm
*
Y
N
Performs Drill function
EVACUATE SWITCH
non-alarm*
Y
N
Performs Drill function, activates silenceable fire outputs
FIRE CONTROL
non-alarm
N
Y
Monitors non-fire activations
NON FIRE
non-alarm
N
Y
Monitors non-fire activations
NC NON FIRE
non-alarm
N
Y
Monitors non-fire activations, where an open circuit=active.
PAS INHIBIT
non-alarm
N
N
Inhibits Positive Alarm Sequence
POWER MONITR
trouble
†
N
N
Monitors main and auxiliary power supplies (use trouble zones for
activations)
RESET SWITCH
non-alarm
N
N
Performs Reset function
SIL SWITCH
non alarm
N
N
Performs Signal Silence function
TELE PAGE
non-alarm
N
Y
Performs function of page button on FFT-7. Allows remote paging
to a fire area
DISABLE MON
disable
N
N
When this point activates it will create a disable on the panel for that
point. No CBE generated. Modules can not be disabled via ACS,
Alter Status, or over the network.
TROUBLE MON
trouble
N
N
Monitors trouble inputs (use trouble zones for activations)
Blank
fire alarm
Y
Y
Monitors for a device with no description
HEAT DETECT
fire alarm
Y
Y
Monitors for conventional heat detector
RF MON MODUL
fire alarm
Y
Y
Wireless alarm-monitoring device
RF PULL STA
fire alarm
Y
Y
Wireless manual fire-alarm-activating device
RF SUPERVSRY
supervisory
N
Y
Wireless supervisory-monitoring device
ABORT SWITCH
non-alarm
N
Y
Provides an abort function through a monitor module (connected to
a UL-listed abort station) for a releasing zone.
MAN RELEASE
fire alarm
‡
Y
Y
Provides a manual release through a monitor module (connected to
a UL-listed pull station) for a releasing zone
MAN REL DELAY
fire alarm†
Y
Y
Provides a manual release with a 10-second delay through a
monitor module (connected to a UL-listed pull station) for a
releasing zone
SECOND SHOT
fire alarm†
Y
Y
Provides a second manual release through a monitor module
(connected to a UL-listed pull station) for a releasing zone
HAZARD ALRT
non-fire
N
Y
Monitors for a hazard alert
WEATHER ALRT
non-fire
N
Y
Monitors for a weather alert
PROCESS MON
critical process
Y
Y
Monitors for a critical process
Type Code
Point Type
Point Characteristics
Latching
(Y=yes
N=no)
Activates
CBE
Device Function
Table G.2 Type Codes for Monitor Modules (2 of 3)