NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
139
Type Codes for Input Devices
Type Codes
G.3.3 Type Codes for Monitor Modules
Following is a list of monitor module Type Codes, which can be used to change the function of a
monitor module point.
SUP T(PHOTO)*†
supervisory
N
Y
Photoelectric smoke detector
SMOKE(DUCTP)
fire
Y
Y
Duct Photoelectric smoke detector
SUP L(DUCTP)
supervisory
Y
Y
Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm
SUP T(DUCTP)†
supervisory
N
Y
Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm.
RFSMOKE(PHOTO)
fire
Y
Y
Wireless Photoelectric smoke detector
SMOKE(HARSH)
fire
Y
Y
HARSH smoke detector
SMOKE(LASER)
fire
Y
Y
Laser smoke detector
SUP T (LASER)*†
supervisory
N
Y
Laser Smoke Detector
SUP L (LASER)*
supervisory
Y
Y
Laser Smoke Detector
SMOKE(DUCTL)
fire
Y
Y
Duct Laser smoke detector
SUP L(DUCTL)
supervisory
Y
Y
Laser smoke detector used as a duct detector to report supervisory
condition rather than alarm.
SUP T(DUCTL)
supervisory
N
Y
Laser smoke detector used as a duct detector to report supervisory
condition rather than alarm.
PHOTO/CO
fire
Y
Y
Combination Photoelectric/CO detector
P/CO (P SUP)*
fire
Y
Y
Combination Photoelectric/CO detector. Photo element activation
generates a supervisory condition.
P/CO (C SUP)
fire
Y
Y
Combination Photoelectric/CO detector. CO element activation
generates a supervisory condition.
AIR REF
fire
Y
Y
Assign to one or more FSL-751detectors used to monitor the quality of
air entering the protected area. The air quality measurement allows the
VIEW system to compensate for vehicle fumes, fog, or other particles
brought into the protected area through the ventilation system. Poor air
quality will lower the sensitivity of all FSL-751 detectors on the SLC.
The detector sensitivity, however, remains within approved limits
(always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive level—AL:9 and PA:9
Alarm and Pre-Alarm sensitivity. Refer to “Detector Sensitivity Settings” on page 124 for a complete list of detector sensitivity settings.
HEAT
fire
Y
Y
190
o
F heat detector
HEAT+
fire
Y
Y
190
o
F heat detector with low temperature warning
HEAT(FIXED)
fire
Y
Y
135
o
F intelligent thermal sensor
HEAT (ROR)
fire
Y
Y
15
o
F per minute rate-of-rise detector
SMOKE ACCLIM
fire
Y
Y
Combination Photoelectric/heat detector
SMOKE(ACCLI+)
fire
Y
Y
Combination Photoelectric/heat detector with low temperature
warning,
or
Intelliquad FSC-851 Photoelectric Multi-Criteria Smoke
Sensor.
SMOKE(MULTI)
‡
fire
Y
Y
Multisensor smoke detector
SMOKE(BEAM)
fire
Y
Y
Beam Smoke Detector
* Use only with approval of AHJ
† Not suitable for Canadian applications
‡ CLIP Mode only
Point Characteristics
Type Code
Point Type
Latching
(Y=yes
N=no)
Activates
CBE
Device/Point Function
Table G.1 Intelligent Detector Type Codes (2 of 2)
Type Code
Point Type
Point Characteristics
Latching
(Y=yes
N=no)
Activates
CBE
Device Function
MONITOR
fire alarm
Y
Y
Alarm-monitoring device
NC MONITOR
fire alarm
Y
Y
Alarm monitoring device, where an open circuit=active.
Table G.2 Type Codes for Monitor Modules (1 of 3)