8
MPA1C1 Access Control Unit
You can use the MPA1C1 panel as a standalone panel with inde
-
pendent card and transaction storage or, with a host software
upgrade, as a fully monitored online access control device.
The three panel inputs are capable of four state supervision:
Normal
,
Alarm
,
Short
and
Cut
. One input is used for door status
on each door. There is one tamper input in the MPA1C1.
All three inputs can also be used as additional inputs when not
required for their default purpose. By default non-supervised
inputs are used for Request to Exit (REX) button, Door Position
Switch (DrCnt), and Tamper (T-LID).
Note:
The MPA1C1 can only connect to OSDP readers.
Содержание MPA1C1
Страница 4: ...3 Introduction This document describes how to install the MPA1C1 access control unit ...
Страница 8: ...7 MPA1C1 door with single reader and door strike MPA1C1 door with two readers and door strike ...
Страница 17: ...16 Note The MPA1C1 Controller has been installed already in the MPA1ENCP enclosure ...
Страница 23: ...22 Take out the inner base and turn it facing the labels toward you and snap in the MPA1C1 panel ...