ZX Fire Alarm Control Panels
MORLEY-IAS
Commissioning Manual
Document No. 996-175-000-1, Revision 01
Page 35
•
When shown on the display, the letter ‘P’ appears in front of the address. This indicates the output is
on the peripheral bus. A letter is added after the address to indicate relay A, B, C or D.
•
When peripheral bus units are used, their zone programming selection is shown by using the same
‘Sounder’ option as the on board and loop-driven outputs. For example, a sounder circuit controller
SCC module wired onto the peripheral bus with an address of 11 may be shown as:
[ Panel in Commissioning mode ]
---------------------------------------------
SOUNDER
Pattern
P:011:B
004
•
This shows that all sounders wired into the output 'B' of the sounder circuit controller wired onto the
peripheral bus at address 11 will use ringing pattern 004.
An auto-learn must be performed on the peripherals before they will be added to the list
of sounder circuit outputs.
•
Refer to the 4-Way Sounder Installation Guide for further information.
5.4.5 Overriding Delays at Level 1.
EN54
9
EN54-2 7.11d
Override delays at
Level 1.
It shall be possible to override all delays to outputs at Level 1. Refer
to Section 16.2 for further information.
•
If ZX1Se, ZX2Se, ZX5Se and ZX10Se panels are to be configured
with delays to outputs a manual call point (MCP) will be located
next to the panel to enable any delays to be overridden.
5.4.6 Sounder Fault Monitoring
•
Once commissioned any open or short circuits occurring on any of these inputs, either on-board or
remote, are automatically detected, recorded in the event log and displayed. For example:
[ Panel in Commissioning mode ]
---------------------------------------------
SHORT CIRCUIT ON SOUNDER B