5.5. Online configuration
84
MC Toolkit (MCT404) User Manual
Revision 3
Input Calibration (DE Transmitters) - Correct Input (Zero), LRV, URV; Reset Corrects
Set-Up On Bench
A typical bench set-up is shown at right.
Connect the MC Toolkit as indicated, and
establish communication with the
transmitter.
For these procedures, components in the
current loop are not critical, provided that
they support reliable communication
between the transmitter and the MC Toolkit.
If a Honeywell Pressure Transmitter is being
calibrated, positioning (leveling) is important,
because the meter body contains fluids that
can affect zero sensing.
Enter
(configure)
values for
LRV and
URV
From the DE MAIN MENU, select
Configure
to call up the DE
CONFIGURE display.
a. Use the
PV Units
to select the appropriate Engineering
Units.
b. Using the keyboard, enter the desired
LRV
and
URV
values.
c. Select the
Send
button to copy all newly entered values to
the transmitter. When the copy operation is complete,
Send
will be displayed in half intensity.