4.3 Customizing the settings
Modifying device identification settings
Using the Device Identification settings, you can choose how to detect a device. Devices can be detected
using poll address or device tag name. By default, devices are detected using poll address zero. However,
you can modify these settings based on how you want to detect devices.
To modify the device detection settings, perform the following steps.
Note
: Before modifying the settings, see
1.
On the FDC homepage, tap
Settings
>
Select
.
The
Settings
dialog box appears.
2.
Tap
Device Identification
tab.
3.
If you want to detect a device using the device specific tag name, select
Using Device Tag
checkbox (for HART 5 or later versions) or
Using Device Long Tag
checkbox (for HART 6 or
later versions).
4.
If you want to detect a device using poll address, select
Using Poll Address
check box.
To detect a device using poll address zero, tap
Using poll address 0 only
.
To detect a device using first poll address, tap
Find first poll address and use
. With this setting,
FDC will detect the first device which responds on any poll address during a scan from 0 to 63.
To detect a device using selected poll address, tap
Use selected poll address
and choose the
appropriate poll address using the up and down arrow keys.
For example, if you want to detect a device with poll address 20, press and hold the up or down
arrow key until the poll address 20 appears.
To detect a device using a range of poll addresses, tap
Use From
to choose the device between
the ranges of poll address you want to detect.
For example, if you want to detect a device within the range of poll address 20 and 25, press and
hold the up or down arrows keys to specify the range of poll address.
Modifying DD selection settings
Using the DD selection settings, you can choose how to select a DD file for a device, when a DD with
matching device revision is not present. By default, the option
Always ask user
is selected. To modify
the DD selection settings, perform the following steps.
Note
: Before modifying the DD selection settings, see
1.
On the FDC homepage, tap
Settings
>
Select
The
Settings
dialog box appears.
2.
Tap
DD Selection
tab.
3.
If the DD file with the current device revision is missing for a device, select one of the following:
a)
Use DD file of previous device revision
b)
Use generic DD file
c)
Always ask user.
Содержание MCT404
Страница 1: ...Honeywell Field Solutions MC Toolkit MCT404 User Manual Doc No 34 ST 25 50 Revision 3 Date June 2016 ...
Страница 12: ......
Страница 26: ......
Страница 88: ...5 5 Online configuration 76 MC Toolkit MCT404 User Manual Revision 3 DE Upload Procedures ...
Страница 108: ...5 6 How to view the Saved Configuration file and Import to Excel 96 MC Toolkit MCT404 User Manual Revision 3 ...