5.5. Online configuration
90
MC Toolkit (MCT404) User Manual
Revision 3
Table 16 DE Output Calibration - Trim DAC Current
DE Output Calibration - Trim DAC Current
Overview
of
Objectives
For a DE transmitter
operating in
analog mode
in a user's application, calibrate the
analog
output current
to the PV input range. That is, adjust the output such that 4 mA corresponds
to 0% (LRV), and 20 mA corresponds to 100% (URV).
Call up
display
In the DE MAIN
MENU, select the
Calibration
button.
The CALIBRATION
menu appears.
Select the
Trim DAC Curr.
button; this display appears.