5.5. Online configuration
92
MC Toolkit (MCT404) User Manual
Revision 3
Table 17 DE Calibration - Apply Values
DE Calibration - Apply PV values to Set LRV and Set URV
Overview
of
Objectives
:
Manually set the Process Variable
input to 0%
, and apply this value to
Set LRV
;
Manually set the Process Variable
input to 100%
, and apply this value to
Set URV
.
NOTE:
This procedure applies to DE Transmitters operating in DE Mode as well as to those
operating in Analog (current) Mode.
On the DE MAIN MENU,
select the
Calibration
button.
In the Apply Values group,
select the
Set LRV
button.
The popup message at right
appears.
Note:
The value of the Input
indicated in this
message updates only
when the popup
message is called up.
To update this value,
select the
No
button,
and again select the
Set
LRV
button in the
CALIBRATION display.