 MODULE FOR SINGLE LAMP SELECTION AND MONITORING  

Switching of one selected light in the electric circuit

SET010 select

DIP-switch 1

ON for non-maintained mode
OFF for maintained mode (Default)

DIP-switch 2

OFF for lighting address 1-16 (Default)
ON for lighting address 17-32

Indicator LED

Rotary coding switch

for setting the exact lamp adress

DIP-switch 3 (OFF) 

Attention!

Connect L and N correctly!

Exchanging L and N causes malfunction.

Function 

Setting the lighting address is carried out by a rotary coding switch that is easily accessible from the 
outside. 

By means of a suitable control, it is possible with the aid of the SET010 select to determine whether the 
lamp connected to it is ready for use or faulty.
In the mixed operation circuit, the connected lamp can also be additionally set in non-maintained mode 
or maintained mode (DIP Switch 1).

The address range 17 to 32 can be selected by setting DIP switch 2 to ON. 

The module is already prepared for administering a total of 32 lighting addresses. 

Settings 

Lighting addresses 1 to 16 can be slected when DIP switch 2 is set at OFF. 

(DIP switch 2 = ON and rotary coding switch = 1 is equivalent to lighting address 17 etc.)

Technical description

Cross section:

Temperature:

Dimensions (L x W x H in mm)

78 x 30 x 20

2

Max: 1.5mm

-10°C up to +60°C, T

=+75°C  

cmax

SET

010 select