M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES

63-2612—05

6

Input Signal Override (M7410F)

To override the controller output signal, connect the input 

signal wire with COM (0%) or 24V (100%), see Fig. 11, using 

an external relay.

If the temperature falls below a certain point; for example, 

32°F (0°C), a relay can switch the 24 Vac to the Y connection 

(0 to 10V, 2 to 10V). This opens or closes the valve.

Fig. 11. Input signal override for frost protection.

OPERATION

Apply power to the actuator to drive the synchronous motor to 

turn a screw spindle that opens or closes the valve. The 

actuator is attached to the valve by a hand-tightened coupling 

ring and a magnetic coupling that limit the gear assembly 

torque and the actuator driving force.

The actuator pushes the center stem of the valve down, 

compressing the valve spring and opening the valve. When 

the actuator reverses, the valve spring expands, closing the 

valve and pushing the center stem up.

The valves are supplied with a threaded plastic protective 

cover/manual handle to protect the stem and to allow for 

manual operation. Use the protective cover/manual handle to 

fill the system during initial installation.

Turning the protective cover/manual handle:

— Clockwise: pushes the center stem of the valve down, 

compressing the valve spring and opening the valve.

— Counterclockwise: allows the spring to expand, pushing the 

center stem up and closing the valve.

NOTES:

You can also use the protective cover/handle for 

heating/cooling with neither a controller nor 

actuator during the building construction phase.

Retain the protective cover. It can be needed for 

future manual operation.

Commissioning

A microprocessor within the actuator maintains accurate 

control/positioning by recommissioning itself every 24 hours or 

whenever power is applied or interrupted. When power is 

applied, the actuator drives to 0 and then to its starting 

position according to the starting/input signal. The initial 

commissioning or 24-hour recommissioning takes between 

2.5 and 5 minutes, depending on tholme position of the 

actuator.

Valve Flow

TWO-WAY VALVES

In the two-way valves, the direction of flow is always from inlet 

port to outlet port as indicated by the arrows on the valve body 

(see Fig. 12).

THREE-WAY VALVES

Three-way valves are designed to be used as mixing valves. 

This means that port AB is the total flow outlet; port A is the 

controlled flow inlet; and port B is the bypass inlet 

(see Fig. 13).

Fig. 12. Two-way valve operation block diagram.

Fig. 13. Three-way valve operation block diagram.

M8226B

2

3

1

 = 0 / 2 ... 10V

24 V

2

3

1

 = 0 / 2 ... 10V

24 V

OUTLET

INLET

+

+

M5357A

INLET

OUTLET

AB

B

A

+

AB

B

A

+

M5358

Содержание M6410A

Страница 1: ...ower consumption Synchronous motor No mounting tools required Low maintenance plastic housing Conduit connector standard No separate linkage required M6410A provides 3 position floating control without proportional feedback M7410F receives 0 to 10 Vdc or 2 to 10 Vdc input signal selectable at the site M7410F includes direct reverse acting switch Especially suitable for Excel Controller or Individu...

Страница 2: ...ION Equipment Damage Hazard Installing a high force 67 5 lb 300 N actuator on 1 2 or 3 4 in valve can damage the valve beyond repair Use only Series 1000 40 5 lb 180 N actuators with the smaller 1 2 in and 3 4 in valves IMPORTANT A low force 40 5 lb 180 N actuator installed on a valve larger than 3 4 in cannot operate the valve Install high force actuators 67 5 lb only on large valves 1 in 1 1 4 i...

Страница 3: ...m Pipe Size in in mm Cv Close off Rating psi Two way Three way 1 25 5 5 232 232 7 8 11 1 1 4 32 18 174 174 1 1 2 38 25 145 145 Diameter in For Valve Cv Part Number Two Way 1 V5862A3003 5 5 0903827 V5862A3011 7 8 V5862A3029 11 1 1 4 V5862A3037 18 0903828 1 1 2 V5862A3045 25 0903829 Three Way 1 V5863A3002 5 5 0903827 V5863A3010 7 8 V5863A3028 11 1 1 4 V5863A3036 18 0903828 1 1 2 V5863A3044 25 090382...

Страница 4: ... actuator are accessible Mounting Valve The valve body should be completely installed in the pipe line before the actuator is installed 1 Verify pipe size and flow direction for the valve being used 2 Position the valve so that the actuator can be easily installed 3 Install the valve using the applicable tools and supplies Follow standard practices Actuator No tools are required to install the act...

Страница 5: ...ONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M19616 OPEN CLOSE COMMON L1 HOT L2 1 M19552 1 OPEN SIGNAL CLOSED SIGNAL 1 2 3 4 5 6 7 8 9 10 11 12 24V 24V COM COM OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 W7751D F SUBBASE TRIAC EQUIVALENT CIRCUIT M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN REHEATER M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN PERIPHERAL HEATER 1 TERMINALS 1...

Страница 6: ...ise pushes the center stem of the valve down compressing the valve spring and opening the valve Counterclockwise allows the spring to expand pushing the center stem up and closing the valve NOTES You can also use the protective cover handle for heating cooling with neither a controller nor actuator during the building construction phase Retain the protective cover It can be needed for future manua...

Страница 7: ...e packed with the WV3000R Insert Replacement Tool 3 Make sure the cartridge insert O ring is properly seated and not damaged 4 After installing the actuator check actuator operation Actuator Perform a functional checkout of the M6410A Actuator as follows 1 Change the room temperature setpoint by at least 10 F 6 C 2 Make sure the actuator either opens or closes the valve depending on the direction ...

Страница 8: ...l Inc 63 2612 05 M S Rev 02 13 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modifi...

Отзывы: