Honeywell M6410A Скачать руководство пользователя страница 1

PRODUCT DATA

Put Bar Code Here

63-2612-05

M6410A, M7410F Actuators;

V5862A, V5863A Valves

67.5 LB (300N) NON-SPRING RETURN ACTUATORS

AND 1, 1-1/4, 1-1/2 INCH NPT CARTRIDGE GLOBE VALVES

 APPLICATION

M6410A and M7410F Series 3000 Non-Spring Return Valve 

Actuators provide floating or modulating control of V5862A 

and V5863A Series 3000 Cartridge Globe Valves.

The actuators are used in electronic temperature control 

systems, which use hot and/or cold water (with glycol up to 

50 percent) as the controlled medium in variable air volume 

(VAV) terminal units, fan-coil units, small reheaters and 

recoolers.

FEATURES

• Small size allows installation in limited space.

• Long stroke allows wider range of control.

Actuators

• Low power consumption.

• Synchronous motor.

• No mounting tools required.

• Low-maintenance plastic housing.

• Conduit connector standard.

• No separate linkage required.

• M6410A provides 3-position floating control without 

proportional feedback.

• M7410F receives 0 to 10 Vdc or 2 to 10 Vdc input 

signal, selectable at the site.

• M7410F includes direct/reverse acting switch.

• Especially suitable for Excel

®

 Controller or Individual 

Room Controller (IRC) System.

• Internal valve position indicator.

• Magnetic coupling for torque limitation independent of 

voltage supply, and self-adjustment of close-off port.

• Ready-to-wire connecting cable.

Valves

• V5862A is a two-way female NPT valve.

• V5863A is a three-way female NPT mixing valve.

• Pressure-balanced plug.

• Soft valve seat provides low leakage rate.

• Valve inserts are changeable with the insert 

replacement tool.

• Threaded plastic cover allows manual operation.

• Brass body and stainless steel stem.

Содержание M6410A

Страница 1: ...ower consumption Synchronous motor No mounting tools required Low maintenance plastic housing Conduit connector standard No separate linkage required M6410A provides 3 position floating control without proportional feedback M7410F receives 0 to 10 Vdc or 2 to 10 Vdc input signal selectable at the site M7410F includes direct reverse acting switch Especially suitable for Excel Controller or Individu...

Страница 2: ...ION Equipment Damage Hazard Installing a high force 67 5 lb 300 N actuator on 1 2 or 3 4 in valve can damage the valve beyond repair Use only Series 1000 40 5 lb 180 N actuators with the smaller 1 2 in and 3 4 in valves IMPORTANT A low force 40 5 lb 180 N actuator installed on a valve larger than 3 4 in cannot operate the valve Install high force actuators 67 5 lb only on large valves 1 in 1 1 4 i...

Страница 3: ...m Pipe Size in in mm Cv Close off Rating psi Two way Three way 1 25 5 5 232 232 7 8 11 1 1 4 32 18 174 174 1 1 2 38 25 145 145 Diameter in For Valve Cv Part Number Two Way 1 V5862A3003 5 5 0903827 V5862A3011 7 8 V5862A3029 11 1 1 4 V5862A3037 18 0903828 1 1 2 V5862A3045 25 0903829 Three Way 1 V5863A3002 5 5 0903827 V5863A3010 7 8 V5863A3028 11 1 1 4 V5863A3036 18 0903828 1 1 2 V5863A3044 25 090382...

Страница 4: ... actuator are accessible Mounting Valve The valve body should be completely installed in the pipe line before the actuator is installed 1 Verify pipe size and flow direction for the valve being used 2 Position the valve so that the actuator can be easily installed 3 Install the valve using the applicable tools and supplies Follow standard practices Actuator No tools are required to install the act...

Страница 5: ...ONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M19616 OPEN CLOSE COMMON L1 HOT L2 1 M19552 1 OPEN SIGNAL CLOSED SIGNAL 1 2 3 4 5 6 7 8 9 10 11 12 24V 24V COM COM OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 W7751D F SUBBASE TRIAC EQUIVALENT CIRCUIT M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN REHEATER M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN PERIPHERAL HEATER 1 TERMINALS 1...

Страница 6: ...ise pushes the center stem of the valve down compressing the valve spring and opening the valve Counterclockwise allows the spring to expand pushing the center stem up and closing the valve NOTES You can also use the protective cover handle for heating cooling with neither a controller nor actuator during the building construction phase Retain the protective cover It can be needed for future manua...

Страница 7: ...e packed with the WV3000R Insert Replacement Tool 3 Make sure the cartridge insert O ring is properly seated and not damaged 4 After installing the actuator check actuator operation Actuator Perform a functional checkout of the M6410A Actuator as follows 1 Change the room temperature setpoint by at least 10 F 6 C 2 Make sure the actuator either opens or closes the valve depending on the direction ...

Страница 8: ...l Inc 63 2612 05 M S Rev 02 13 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modifi...

Отзывы: