M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES

3

63-2612—05

Actuator Required:

M6410A: Non-Spring Return Valve Actuator (3-position 

floating).

M7410F: 0 to 10 Vdc or 2 to 10 Vdc Electronic Actuator.

Valve inserts are provided as spare parts. See Table 2.

Leakage Rate: 

0.05% of Cv.

Valve Close-off Ratings: 

See Table 1.

Approvals (Actuators): 

Underwriters Laboratories Inc. listed 

for plenum use (UL94-5V).

Accessories and Replacement Parts:

WV3000R Insert Replacement Tool, for replacing cartridge 

insert.

Table 1. Valve Close-off Ratings.

Table 2. Valve Insert Replacement Parts.

Fig. 1. Dimensions of V5862A and V5863A in in. (mm).

Fig. 2. Non-Spring Return Actuator (M6410, M7410) 

dimensions in in. (mm).

Pipe Size in 

in. (mm)

C

v

Close-off Rating (psi)

Two-way

Three-way

1 (25)

5.5

232

232

7.8
11

1-1/4 (32)

18

174

174

1-1/2 (38)

25

145

145

Diameter (in.)

For Valve

Cv

Part Number

Two-Way

 1

V5862A3003

5.5

0903827

V5862A3011

7.8

V5862A3029

11

1-1/4

V5862A3037

18

0903828

1-1/2

V5862A3045

25

0903829

Three-Way

 1

V5863A3002

5.5

0903827

V5863A3010

7.8

V5863A3028

11

1-1/4

V5863A3036

18

0903828

1-1/2

V5863A3044

25

0903829

M19693

M19619C

INLET

OUTLET

PORT A

PORT AB

PORT B

V5863 FLOW

V5862A3 FLOW

1 (25)
1-1/4 (32)
1-1/2 (38)

4-1/8 (105)

4-15/16 (125)

5-1/8 (130)

1-5/8 (41)

2 (50)

2-3/16 (55)

2-1/16 (53)
2-7/16 (62)
2-9/16 (65)

3-5/8 (92)
3-5/8 (92)
3-7/8 (98)

B

C

D

E

2-5/16 (58)
2-5/16 (58)

2-11/16 (69)

G

2  (50)

2-3/16 (55)
2-9/16 (65)

F

VALVE SIZE

A (mm)

E

A

C

C

F

B

D

23/32

(18)

G

1/4 (6)

STROKE

MINIMUM CLEARANCE

9-7/8

(250)

FLOW DIAGRAM 

FOR 1, 1-1/4 AND 1-1/2 INCH VALVES

M8225A

3-15/16

(100)

1/2 (13)

1-15/16

(49)

2-3/8  (61)

2-5/16  (58)

Содержание M6410A

Страница 1: ...ower consumption Synchronous motor No mounting tools required Low maintenance plastic housing Conduit connector standard No separate linkage required M6410A provides 3 position floating control without proportional feedback M7410F receives 0 to 10 Vdc or 2 to 10 Vdc input signal selectable at the site M7410F includes direct reverse acting switch Especially suitable for Excel Controller or Individu...

Страница 2: ...ION Equipment Damage Hazard Installing a high force 67 5 lb 300 N actuator on 1 2 or 3 4 in valve can damage the valve beyond repair Use only Series 1000 40 5 lb 180 N actuators with the smaller 1 2 in and 3 4 in valves IMPORTANT A low force 40 5 lb 180 N actuator installed on a valve larger than 3 4 in cannot operate the valve Install high force actuators 67 5 lb only on large valves 1 in 1 1 4 i...

Страница 3: ...m Pipe Size in in mm Cv Close off Rating psi Two way Three way 1 25 5 5 232 232 7 8 11 1 1 4 32 18 174 174 1 1 2 38 25 145 145 Diameter in For Valve Cv Part Number Two Way 1 V5862A3003 5 5 0903827 V5862A3011 7 8 V5862A3029 11 1 1 4 V5862A3037 18 0903828 1 1 2 V5862A3045 25 0903829 Three Way 1 V5863A3002 5 5 0903827 V5863A3010 7 8 V5863A3028 11 1 1 4 V5863A3036 18 0903828 1 1 2 V5863A3044 25 090382...

Страница 4: ... actuator are accessible Mounting Valve The valve body should be completely installed in the pipe line before the actuator is installed 1 Verify pipe size and flow direction for the valve being used 2 Position the valve so that the actuator can be easily installed 3 Install the valve using the applicable tools and supplies Follow standard practices Actuator No tools are required to install the act...

Страница 5: ...ONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M19616 OPEN CLOSE COMMON L1 HOT L2 1 M19552 1 OPEN SIGNAL CLOSED SIGNAL 1 2 3 4 5 6 7 8 9 10 11 12 24V 24V COM COM OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 W7751D F SUBBASE TRIAC EQUIVALENT CIRCUIT M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN REHEATER M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN PERIPHERAL HEATER 1 TERMINALS 1...

Страница 6: ...ise pushes the center stem of the valve down compressing the valve spring and opening the valve Counterclockwise allows the spring to expand pushing the center stem up and closing the valve NOTES You can also use the protective cover handle for heating cooling with neither a controller nor actuator during the building construction phase Retain the protective cover It can be needed for future manua...

Страница 7: ...e packed with the WV3000R Insert Replacement Tool 3 Make sure the cartridge insert O ring is properly seated and not damaged 4 After installing the actuator check actuator operation Actuator Perform a functional checkout of the M6410A Actuator as follows 1 Change the room temperature setpoint by at least 10 F 6 C 2 Make sure the actuator either opens or closes the valve depending on the direction ...

Страница 8: ...l Inc 63 2612 05 M S Rev 02 13 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modifi...

Отзывы: