M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES
3
63-2612—05
Actuator Required:
M6410A: Non-Spring Return Valve Actuator (3-position
floating).
M7410F: 0 to 10 Vdc or 2 to 10 Vdc Electronic Actuator.
Valve inserts are provided as spare parts. See Table 2.
Leakage Rate:
≤
0.05% of Cv.
Valve Close-off Ratings:
Approvals (Actuators):
Underwriters Laboratories Inc. listed
for plenum use (UL94-5V).
Accessories and Replacement Parts:
WV3000R Insert Replacement Tool, for replacing cartridge
insert.
Table 1. Valve Close-off Ratings.
Table 2. Valve Insert Replacement Parts.
Fig. 1. Dimensions of V5862A and V5863A in in. (mm).
Fig. 2. Non-Spring Return Actuator (M6410, M7410)
dimensions in in. (mm).
Pipe Size in
in. (mm)
C
v
Close-off Rating (psi)
Two-way
Three-way
1 (25)
5.5
232
232
7.8
11
1-1/4 (32)
18
174
174
1-1/2 (38)
25
145
145
Diameter (in.)
For Valve
Cv
Part Number
Two-Way
1
V5862A3003
5.5
0903827
V5862A3011
7.8
V5862A3029
11
1-1/4
V5862A3037
18
0903828
1-1/2
V5862A3045
25
0903829
Three-Way
1
V5863A3002
5.5
0903827
V5863A3010
7.8
V5863A3028
11
1-1/4
V5863A3036
18
0903828
1-1/2
V5863A3044
25
0903829
M19693
M19619C
INLET
OUTLET
PORT A
PORT AB
PORT B
V5863 FLOW
V5862A3 FLOW
1 (25)
1-1/4 (32)
1-1/2 (38)
4-1/8 (105)
4-15/16 (125)
5-1/8 (130)
1-5/8 (41)
2 (50)
2-3/16 (55)
2-1/16 (53)
2-7/16 (62)
2-9/16 (65)
3-5/8 (92)
3-5/8 (92)
3-7/8 (98)
B
C
D
E
2-5/16 (58)
2-5/16 (58)
2-11/16 (69)
G
2 (50)
2-3/16 (55)
2-9/16 (65)
F
VALVE SIZE
A (mm)
E
A
C
C
F
B
D
23/32
(18)
G
1/4 (6)
STROKE
MINIMUM CLEARANCE
9-7/8
(250)
FLOW DIAGRAM
FOR 1, 1-1/4 AND 1-1/2 INCH VALVES
M8225A
3-15/16
(100)
1/2 (13)
1-15/16
(49)
2-3/8 (61)
2-5/16 (58)