M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES

63-2612—05

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not 

include normal manufacturing tolerances. Therefore, 

an individual unit may not exactly match the listed 

specifications. Also, this product is tested and 

calibrated under closely controlled conditions and 

some minor differences in performance can be 

expected if those conditions are changed.

Models:

M6410A: Non-Spring Return Valve Actuator. Provides floating 

control of the V5862A and V5863A Valves.

M7410F: Non-Spring Return Valve Actuator. Provides 

modulating control of V5862A and V5863A Valves.

V5862A: Two-way NPT Valves.

V5863A: Three-way NPT Mixing Valves.

CAUTION

Equipment Damage Hazard.

Installing a high-force (67.5 lb [300 N]) actuator on 

1/2 or 3/4 in. valve can damage the valve beyond 

repair.

Use only Series 1000 (40.5 lb [180 N]) actuators with 

the smaller (1/2 in. and 3/4 in.) valves.

IMPORTANT

— A low-force (40.5 lb [180 N]) actuator installed on a 

valve larger than 3/4 in. cannot operate the valve.

— Install high-force actuators (67.5 lb) only on large 

valves (1 in., 1-1/4 in., 1-1/2 in.).

Dimensions:

Valves: See Fig. 1.

Actuators: See Fig. 2.

Control Modes:

M6410A: Floating.

M7410F: Modulating.

Ambient Ratings:

Operating Temperature Range: 32° to 122°F (0° to 50°C).

Storage Temperature Range: -40° to 158°F (-40° to 70°C).

Humidity Range: 5 to 95% RH (noncondensing).

Electrical Ratings:

Input Power: 24 Vac, +10/-30 percent, 50/60 Hz.

Power Consumption:

M6410A: 0.7 VA.

M7410F: 1.4 VA.

Input Signal (M7410F): Modulating (adjustable) 0 to 10V, 

2 to 10V, 0.1 mA.

Input Impedance (M7410F): 100K ohms.

Mounting: 

Actuator screws onto valve body.

Connections: 

4.9 ft (1.5m) cable.

Weight:

M6410A: 5 oz (0.15 kg).

M7410F: 5.6 oz (0.16 kg).

Stroke: 

1/4 in. (6.5 mm).

Running Time:

At 50 Hz: 150 seconds.

At 60 Hz: 125 seconds.

Stem Force: 

67.5 lb (300 N).

Suitable Medium: 

Water with maximum 50% glycol.

Controlled Water Temperature: 

36° to 230°F (2° to 110°C).

Rangeability:

Two-way Valve: 50:1.

Three-way Valve: 50:1 for controlled port (A to AB).

Flow Characteristic: 

Linear.

Valve Cv Rating: 

See Table 1.

NOTE: To determine the capacity index (Cv) needed for 

your application, use the following formula: Cv = 

gallons per minute divided by the square root of 

the pressure drop across the valve when the 

valve is fully open.

Body Material: 

Brass.

Stem and Plug Assembly:

Stem: Stainless steel.

Plug: Brass.

Содержание M6410A

Страница 1: ...ower consumption Synchronous motor No mounting tools required Low maintenance plastic housing Conduit connector standard No separate linkage required M6410A provides 3 position floating control without proportional feedback M7410F receives 0 to 10 Vdc or 2 to 10 Vdc input signal selectable at the site M7410F includes direct reverse acting switch Especially suitable for Excel Controller or Individu...

Страница 2: ...ION Equipment Damage Hazard Installing a high force 67 5 lb 300 N actuator on 1 2 or 3 4 in valve can damage the valve beyond repair Use only Series 1000 40 5 lb 180 N actuators with the smaller 1 2 in and 3 4 in valves IMPORTANT A low force 40 5 lb 180 N actuator installed on a valve larger than 3 4 in cannot operate the valve Install high force actuators 67 5 lb only on large valves 1 in 1 1 4 i...

Страница 3: ...m Pipe Size in in mm Cv Close off Rating psi Two way Three way 1 25 5 5 232 232 7 8 11 1 1 4 32 18 174 174 1 1 2 38 25 145 145 Diameter in For Valve Cv Part Number Two Way 1 V5862A3003 5 5 0903827 V5862A3011 7 8 V5862A3029 11 1 1 4 V5862A3037 18 0903828 1 1 2 V5862A3045 25 0903829 Three Way 1 V5863A3002 5 5 0903827 V5863A3010 7 8 V5863A3028 11 1 1 4 V5863A3036 18 0903828 1 1 2 V5863A3044 25 090382...

Страница 4: ... actuator are accessible Mounting Valve The valve body should be completely installed in the pipe line before the actuator is installed 1 Verify pipe size and flow direction for the valve being used 2 Position the valve so that the actuator can be easily installed 3 Install the valve using the applicable tools and supplies Follow standard practices Actuator No tools are required to install the act...

Страница 5: ...ONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M19616 OPEN CLOSE COMMON L1 HOT L2 1 M19552 1 OPEN SIGNAL CLOSED SIGNAL 1 2 3 4 5 6 7 8 9 10 11 12 24V 24V COM COM OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 W7751D F SUBBASE TRIAC EQUIVALENT CIRCUIT M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN REHEATER M6410 SERIES 60 VALVE ACTUATOR STEM UP COM STEM DOWN PERIPHERAL HEATER 1 TERMINALS 1...

Страница 6: ...ise pushes the center stem of the valve down compressing the valve spring and opening the valve Counterclockwise allows the spring to expand pushing the center stem up and closing the valve NOTES You can also use the protective cover handle for heating cooling with neither a controller nor actuator during the building construction phase Retain the protective cover It can be needed for future manua...

Страница 7: ...e packed with the WV3000R Insert Replacement Tool 3 Make sure the cartridge insert O ring is properly seated and not damaged 4 After installing the actuator check actuator operation Actuator Perform a functional checkout of the M6410A Actuator as follows 1 Change the room temperature setpoint by at least 10 F 6 C 2 Make sure the actuator either opens or closes the valve depending on the direction ...

Страница 8: ...l Inc 63 2612 05 M S Rev 02 13 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modifi...

Отзывы: