Honeywell GmbH
19
MU1H-1408GE23 R0305
GB
Disturbance
Cause
Remedy
No brine intake
Incorrect settings at the control valve
Check the control valve settings
(
☞
Chapter 9)
Sewerage tube is blocked
Clean and, if necessary, replace sewerage tube
(CS)
Min. operating pressure not available
Min. operating pressure is 1.8 bar
(
☞
Chapter 3)
Permanent discharge into
sewerage tube
Back pressure in sewerage tube is too high
Clean and, if necessary, replace sewerage tube
(CS)
Control head is defective
Call the Technical Customer Service on
(49) 6261 810
High salt consumption
Incorrect settings at the control valve
Check the control valve settings
(
☞
Chapter 9)
Blending has been set incorrectly
Check blending valve and mixing ratio
(
☞
Chapter 7.8)
Too much water in the storage tank
☞
Fault “too much water in the storage tank”
No or insufficient salt con-
sumption
Incorrect settings at the control valve
Check the control valve settings
(Chapter 9. )
Blending has been set incorrectly
Check blending valve and mixing ratio
(
☞
Chapter 7.8)
Brine tube is contaminated
Clean brine tube
Saline water
Min. operating pressure not available
Min. operating pressure is 1.8 bar
(
☞
Chapter 3)
Incorrect settings at the control valve
Check the control valve settings
(
☞
Chapter 9)
Brine valve is contaminated or defective
Clean and, if necessary, replace brine valve
(CS)
1
Control head is defective
Call the Technical Customer Service on
(49) 6261 810
Differential pressure at the
device is too high
Construction of the device is too small
Call the Technical Customer Service on
(49) 6261 810
Blending has been closed too widely
Check blending and mixing ratio
Pressure water supply is not smooth Check functioning of the pressure reducer in
front of the device
Install pressure reducer in front of the device
(
☞
Chapter 6.1)
1. CS = Customer Service