![Honeywell IFP-2100 Скачать руководство пользователя страница 214](http://html.mh-extra.com/html/honeywell/ifp-2100/ifp-2100_installation-and-operation-manual_148864214.webp)
LS10143-001SK-E
Reporting
12-4
SBUS expander trouble
ET
Exp. ID
ETNNXX0000
1
333
Exp. ID
000
SBUS expander trouble restore
ER
Exp. ID
ERNNXX0000
3
333
Exp. ID
000
SLC class A supervision trouble
ET
Exp. ID
ETNNXX0000
1
331
Exp. ID
000
SLC class A supervision trouble
restore
ER
Exp. ID
ERNNXX0000
3
331
Exp. ID
000
SLC programming ended, system
active
TE
0
TENN000000
3
607
00
000
SLC programming started, sys
-
tem shut down
TS
0
TSNN000000
1
607
00
000
SLC short circuit trouble
ET
Exp. ID
ETNNXX0000
1
332
Exp. ID
000
SLC short circuit trouble restore
ER
Exp. ID
ERNNXX0000
3
332
Exp. ID
000
Time changed event
JT
0
JTNN000000
1
625
00
000
Unable to report to account
trouble
RT
Receiver # RTNN00RRRR
1
354
00
Receiver
#
Unable to report to account
trouble restore
YK
Receiver # YKNN00RRRR
3
354
00
Receiver
#
User access code changed
JV
0
JVNN000000
1
602
00
000
User initiated manual dialer test
RX
0
RXNN000000
1
601
00
000
Walk test begin
TS
0
TSNN000000
1
607
00
000
Walk test end
TE
0
TENN000000
3
607
00
000
Zone Events
Note:
Zone events are reported only when “Report by Zone” is selected
Auxiliary power trouble
FT
0000
FTNN000000
1
320
00
000
Auxiliary power trouble restore
FJ
0000
FJNN000000
3
320
00
000
CO Detector Alarm
GA
Zone #
GANN000ZZZ
1
162
00
Zone #
CO Detector Alarm Restore
GH
Zone #
GHNN000ZZZ
3
162
00
Zone #
CO Detector Supervisory Alarm
GS
Zone #
GSNN000ZZZ
1
200
00
Zone #
CO Detector Supervisory Alarm
Restore
GR
Zone #
GRNN000ZZZ
3
200
00
Zone #
CO Detector Trouble
GT
Zone #
GTNN000ZZZ
1
373
00
Zone #
CO Detector Trouble Restore
GJ
Zone #
GJNN000ZZZ
3
373
00
Zone #
Detector Alarm
FA
Zone #
FANN000ZZZ
1
110
00
Zone #
Detector Alarm Restore
FH
Zone #
FHNN000ZZZ
3
110
00
Zone #
Detector trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Detector trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
ECS Switch Trouble
QT
0
QTNN000000
1
242
00
000
ECS Switch Trouble Restore
QJ
0
QJNN000000
3
242
00
000
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
IFP-2100/ECS
Event Description
Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Содержание IFP-2100
Страница 95: ...LS10143 001SK E Networking 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 127: ...LS10143 001SK E Programming Overview 8 8 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns ...
Страница 256: ...Cut Along the Dotted Line ...
Страница 258: ...Cut Along the Dotted Line ...
Страница 260: ...Cut Along the Dotted Line ...
Страница 262: ...Cut Along the Dotted Line ...
Страница 263: ......