![Honeywell IFP-2100 Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/honeywell/ifp-2100/ifp-2100_installation-and-operation-manual_148864103.webp)
LS10143-001SK-E
Network Management
6-6
6.2.6.4 Communicator Reporting Table
The Communicator Report Table specifies event reporting for each panel on the network. Each row in the table
specifies a panel, event types to report, primary and backup receiver numbers, and report by point or zone.
Associated with the receivers are account number and daily test option. The table can have up to 99 rows.
1.
From the main menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
4.
Select 4 for Communicator Reporting Table.
5.
Press * to add rows, Press ENTER to edit data
Figure 6-1 Communicator Reporting
6.3
Voice Options
6.3.1
Edit Timers
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 1 for Edit Timers
6.3.1.1 Control Lockout
The Control Lockout countdown timer is set to the programmed value when an LOC gains ECS Control. The
timer starts over upon any key press at the ECS Control LOC. While the Control Lockout timer is active, an LOC
of equal priority must request ECS control. The Control Lockout timer is cleared when ECS Control is
relinquished. The Control Lockout timer does not apply to ECS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec
UNUSED
Reporting Format
Содержание IFP-2100
Страница 95: ...LS10143 001SK E Networking 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 127: ...LS10143 001SK E Programming Overview 8 8 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns ...
Страница 256: ...Cut Along the Dotted Line ...
Страница 258: ...Cut Along the Dotted Line ...
Страница 260: ...Cut Along the Dotted Line ...
Страница 262: ...Cut Along the Dotted Line ...
Страница 263: ......