Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9-25
old alarm time is reached or the message is validated).
Figure 9-11 AlarmNet Timers
9.6.1.5 Phone Line Gains
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 5 for Phone Line Gains
6.
The available options: *default
•
Dialing Gain:
•
Low = 9 DB Attenuation
•
Normal = 6 DB Attenuation
•
*High = 3 DB Attenuation
•
Reporting Gain:
•
*Low = 9 DB Attenuation
•
Normal = 6 DB Attenuation
•
High = 3 DB Attenuation
9.6.2
Daytime/Nighttime Sensitivity
If you need to change the time that sensitivity levels take effect (that is, the time that “Day” and “Night” begin),
follow these steps.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
Select 2 for Daytime/Nighttime Sensitivity.