Appendix 4
–
Commercial Fire 6-hour Supervision
The NFPA 72 2013 Edition updated the requirement to supervise the transmission path at least once every 6
hours, from an earlier version of 24 hours. This requirement is upheld in 2016 edition as well. Telguard
commercial and fire products support this feature, and it must be enabled for each subscriber by selecting
6-hour supervision during registration.
Appendix 5
–
Compliance with UL and ULC Standards
UL Installation Requirements Summary
Household
Burglary
Househol
d Fire
Household
Burg/Fire
Combinatio
n
Central
Station
Burg
Central
Station
Burg
Police
Connect
Burg
Grade A
Bank, Safe
and Vault
Commercia
l Fire
Commercial
Fire &
Central
Station Burg
TG-7
TG-7 or
TG7FS
TG-7 or
TG-7FS
TG-7
TG-7A
TG-7A
TG-7A
TG-7FS
TG-7A
Telguard
Model
O
O
O
Y
Y
Y
Y*
O
Y
UL Listed Bell
and Bell
Housing **
O
O
O
O
O
O
Y
Y
Y
AC transformer
lines in flexible
conduit.
Y
Y
Y
Y
Y
Y
Y
Y
Y
AC transformer
plugged into
un-switched
outlet.
O
O
O
O
O
O
Y
Y
Y
AC transformer
plugged into
dedicated
branch circuit.
-
-
-
N
N
N
N
N
N
PBX
connection to
RJ31X jack.
O
O
O
O
Y
Y
Y
O
Y
Enclosure
Tamper Switch
connected to
24-hour circuit.
O
O
O
O
Y
Y
Y
Y
Y
Antenna cable
in flexible
conduit
concealed
O
O
O
O
Y
Y
Y
O
Y
Attack resistant
enclosure
(APC-32S).
24 hrs. Use
7ah.
24 hrs.
Use 7ah.
24 hrs. Use
7ah.
24 hrs.
Use 7ah.
24 hrs.
Use 7ah.
24 hrs.
Use 7ah.
72 hrs.
Use 7ah
24 hrs. Use
7ah.
24 hrs. Use
7ah.
12V. Battery
backup
requirement. #
*
Must be connected to alarm panel UL Listed for Bank and Vault
**
Use Mercantile Listed bell and bell housing
# This requirement may be met by powering the TG-7 Series device from a DC alarm panel that has battery backup.
O=Optional (Not Required) Y=Yes (Required) N=No (Not Allowed)