Product Installation Document

This product follows under the UL1481 Fire Alarm Systems, UL603 Burglary Alarm Systems and UL294 Access Control 
Systems. The HP300ULX unit is to be installed in a fail safe mode unless authorized by the local AHJ. This product must 
be installed in compliance with Article 760 of the National Electrical Code, NFPA70, as well as NFPA72 National Fire 
Alarm Code and all applicable local codes. 

1 Description

The HP300ULX is a 12VDC or 24VDC power supply with AC fail and Battery fail supervision.  The unit has not been 
evaluated as elevator equipment, and is not authorized for bell output in Mercantile applications.

2 Specifications

1. Input voltage: 120VAC 60Hz; Current: 1.50A max.
2. Output Voltage: 12VDC or 24VDC, jumper selectable; Current: 2.5A continuous output maximum, 2.0A plus battery 

charger (not supervised).

3. Fail safe dry contact output on AC Failure (within one minute).
4. Built-in charger for sealed lead acid or gel cell type batteries.
5. Instantaneous transfer to stand-by battery on AC failure.
6. Battery presence detection (within 1 minute)
7. Battery low disconnect at 9.90VDC or 19.90VDC.
8. High voltage disconnect at 15VDC or 30VDC.
9. Yellow LED (L3) indication for battery disconnected and battery low.
10. Fail safe dry contact output for Battery trouble (Fail Safe).
11. Battery polarity reversal protection.
12. Thermal overload and short circuit protection.
13. DC output PTC activated indication by Red LED (L2).
14. DC output failure indication by Red LED ( L4 ).
15. AC presence indication by Green LED ( L1 ).
16. DC output indication by Red LED ( L5 ).
17. Battery Leads included.
18. Power Board Dimensions: 5”L x 3.9”W x 1.5”H.
19. Enclosure Dimension: 17”L x 13.5”W x 4.75”H.  Accommodates two 12 Volt 12AH batteries. When using larger 

batteries, a UL approved enclosure must be used.  

3 Installation Instructions

1. Mounting

The power supply should be installed in accordance with all Governing National Electrical and Local Codes.  Mount the 
power supply securely in the desired location using the four (4) mounting holes.

2. Power Supply Input Connection

Continued on next page...

Содержание HP300ULX

Страница 1: ...output on AC Failure within one minute 4 Built in charger for sealed lead acid or gel cell type batteries 5 Instantaneous transfer to stand by battery on AC failure 6 Battery presence detection within 1 minute 7 Battery low disconnect at 9 90VDC or 19 90VDC 8 High voltage disconnect at 15VDC or 30VDC 9 Yellow LED L3 indication for battery disconnected and battery low 10 Fail safe dry contact outpu...

Страница 2: ...osure with the 4 screws and with the Key Lock provided NOTE For UL603 or UL294 applications use a Tamper Switch Catalog number HPVM3 available separately and included enclosure key lock Connect the tamper switch NC outputs to monitoring device to notify of enclosure tampering 4 Maintenance This unit should be tested at least once a year to verify correct operation in accordance with the following ...

Страница 3: ...present Output Battery Capacity STBY ALRM 4Hr Stand By 15Mins ALRM 24Hr Stand By 15Mins ALRM 60Hr Stand By 5Mins ALRM 12Ah 12V STBY 2 00A N A N A ALRM 2 00A N A N A 17Ah 12V STBY 2 00A 200mA N A ALRM 2 00A 2 00A N A 55Ah 12V STBY 2 00A 1 50A 300mA ALRM 2 00A 2 00A 2 00A 12Ah 24V STBY 2 00A N A N A ALRM 2 00A N A N A 17Ah 24V STBY 2 00A 200mA N A ALRM 2 00A 2 00A N A 55Ah 24V STBY 2 00A 1 50A 300mA...

Страница 4: ...0ULX Installation Document P N 52386 A 12 29 05 For additional information Visit our website at http www honeywellpower com Contact Technical Support at 1 877 HPP POWR E mail us at hpp techserv honeywell com ...

Отзывы: