background image

HP300ULX Installation Document  P/N 52386:A  12/29/05

3

5 LED Indications 

6 Battery Stand-By Mode Specification Chart  

LED Number

Power Board (staus when lit)

L1

Green LED - AC present

L2

Red LED - PTC activated

L3

Yellow LED - Battery low or disconnected

L4

Red LED - DC power failure

L5

Red LED - DC output present

Output Battery 

Capacity

STBY/ALRM

4Hr Stand-By 

15Mins/ALRM

24Hr Stand-By 

15Mins/ALRM

60Hr Stand-By 

5Mins/ALRM

12Ah-12V

STBY

2.00A

N/A

N/A

ALRM

2.00A

N/A

N/A

17Ah-12V

STBY

2.00A

200mA

N/A

ALRM

2.00A

2.00A

N/A

55Ah-12V

STBY

2.00A

1.50A

300mA

ALRM

2.00A

2.00A

2.00A

12Ah-24V

STBY

2.00A

N/A

N/A

ALRM

2.00A

N/A

N/A

17Ah-24V

STBY

2.00A

200mA

N/A

ALRM

2.00A

2.00A

N/A

55Ah-24V

STBY

2.00A

1.50A

300mA

ALRM

2.00A

2.00A

2.00A

UL Listing

UL294
UL603

UL294
UL603

UL1481

UL1481

Continued on next page...

Содержание HP300ULX

Страница 1: ...output on AC Failure within one minute 4 Built in charger for sealed lead acid or gel cell type batteries 5 Instantaneous transfer to stand by battery on AC failure 6 Battery presence detection within 1 minute 7 Battery low disconnect at 9 90VDC or 19 90VDC 8 High voltage disconnect at 15VDC or 30VDC 9 Yellow LED L3 indication for battery disconnected and battery low 10 Fail safe dry contact outpu...

Страница 2: ...osure with the 4 screws and with the Key Lock provided NOTE For UL603 or UL294 applications use a Tamper Switch Catalog number HPVM3 available separately and included enclosure key lock Connect the tamper switch NC outputs to monitoring device to notify of enclosure tampering 4 Maintenance This unit should be tested at least once a year to verify correct operation in accordance with the following ...

Страница 3: ...present Output Battery Capacity STBY ALRM 4Hr Stand By 15Mins ALRM 24Hr Stand By 15Mins ALRM 60Hr Stand By 5Mins ALRM 12Ah 12V STBY 2 00A N A N A ALRM 2 00A N A N A 17Ah 12V STBY 2 00A 200mA N A ALRM 2 00A 2 00A N A 55Ah 12V STBY 2 00A 1 50A 300mA ALRM 2 00A 2 00A 2 00A 12Ah 24V STBY 2 00A N A N A ALRM 2 00A N A N A 17Ah 24V STBY 2 00A 200mA N A ALRM 2 00A 2 00A N A 55Ah 24V STBY 2 00A 1 50A 300mA...

Страница 4: ...0ULX Installation Document P N 52386 A 12 29 05 For additional information Visit our website at http www honeywellpower com Contact Technical Support at 1 877 HPP POWR E mail us at hpp techserv honeywell com ...

Отзывы: