Operators manual
© 2017 Honeywell International Inc.
Operators manual underground gas pressure reducing station
Type: HON COCON 13
Page 26
4.5
–
Trouble
shooting
The
cartridge
must
be
readjusted
if
it
is
not
operating
as
required.
The
cartridge's
operating
objectives
are
described
in
paragraph
2.4
on
page
13.
Adjustment
data
can
be
found
in
paragraph
4.4.
Failures
can
be
caused
by:
Problem
1
:
The
outlet
pressure
is
too
high.
Cause
1a
:
The
regulator
pilot
has
not
been
correctly
adjusted.
Solution
1a
:
Read
adjust
the
pilot.
See
paragraph
4.4.
Cause
1b
:
The
regulator
has
failed
open.
The
ssd
valve
is
closed
Solution
1b
:
Replace
the
cartridge
with
a
spare
cartridge.
Check
the
defective
cartridge
in
the
workshop.
Problem
2
:
The
outlet
pressure
is
too
low.
Cause
2a
:
The
regulator
pilot
has
not
been
correctly
adjusted.
Solution
2a
:
Readjust
the
pilot.
See
paragraph
4.7.
Cause
2b
:
The
differential
pressure
p
(p1
–
p2)
is
too
small.
Solution
2b
:
Increase
the
inlet
pressure.
Cause
2c
:
The
filter
is
severely
polluted.
Solution
2c
:
Replace
the
filter
with
a
new
one.
See
paragraph
4.10.3.
.
Problem
3
:
Gas
is
required,
but
is
not
passing
through.
Cause
3a
:
The
ball
valve
is
closed.
Solution
3a
:
Open
the
ball
valve.
Cause
3b
:
The
outlet
valve
is
closed.
Solution
3b
:
Open
the
outlet
valve.
Cause
3c
:
The
valve
in
the
supply
pipe,
located
within
a
distance
of
5
meters
from
the
station's
inlet
has
closed.
Solution
3c
:
Open
the
valve
in
the
supply
pipe.
Cause
3d
:
The
valve
in
the
discharge
pipe,
located
within
a
distance
of
5
meters
of
the
station's
outlet
has
closed.
Solution
3d
:
Open
the
valve
in
the
discharge
pipe.
Cause
3e
:
The
regulator
pilot
has
not
been
correctly
adjusted.
Solution
3e
:
Readjust
the
pilot.
See
paragraph
4.7.
Cause
3f
:
The
ssd
valve
has
closed.
Solution
3f
:
Replace
the
cartridge
with
a
spare
cartridge.
Check
the
defect
cartridge
in
the
workshop.
Problem
5
:
There
is
water
on
the
cartridge.
Cause
5
:
The
cartridge
and
the
pit
cover
seals
are
worn.
Solution
5
:
Replace
the
seal
rings.
Problem
6
:
There
is
dust
in
the
discharge
pipe.
Cause
6
:
The
filter
is
defect.
Solution
6
:
Replace
the
defect
filter
with
a
new
filter.
See
paragraph
4.8.3..