HCL-1PH
User’s
Manual
23
13.2
Operator Menu
oper
•
Push simultaneously
L/R
and
F
for few seconds to
access
to the menu (
Nenu
flashing).
•
Select by arrows
UP
and
DOWN :
oper
then press
F.
•
Select by arrows
UP
and
DOWN :
2
as password
then press
F.
•
You have access to the parameter on
oper
menu.
•
Select by arrows
UP
and
DOWN
the required parameter.
•
If the parameter is
Write/Read (W/R)
press
F
(parameter flashing) then select by
arrows
UP
and
DOWN
the required velue, press
F
to set the new value.
•
Push simultaneously
L/R
and
F
for few seconds to
Exit
from the menu
Maximum output:
Its’ a scaling factor of the Input command signal.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
ουτΝ
OutN
Maximum
output
% 100 0 255 0 100
R/W
100
Power Adjust = 100%
Power Adjust = 80%
Power Adjust = 40%
80
60
40
20
0
40
20
60
100
80
Input %
OUT %
Power output:
This parameter shows the Average power output.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Π
P Power
output
%
−
0
1023
0
100,0
R
Current Limit:
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
ΧΛ
CL Current
Limit
%
0,0
0
1023
0
100,0
R/W
Current output:
This parameter shows the Average current output.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Α
A
Current
output
A
−
0
1023
0
102,3
from 60 to 90A
R
−
0 1023
0 1023
from 120 to 210A
Sample Values and Note