12.7
Schematic
NOTE:
•
*
The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
The semiconductor I2t should be 20% less than power controller I2t.
Semiconductor fuses are classified for UL as supplemetar protection for semiconductor.
They are note approved for branch circuit protection.
•
*²
The auxiliary voltage supply of the HCL unit must be synchronized with load voltage power
supply. If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage
(to the load), use an external transformer as designated.