HCE80(R) / HCC80(R)
Mounting and operation
29
Input/output voltage
230 V AC, 50 Hz
Power consumption
Max. 1750 VA with
connected pump (max. 6 A)
Pump relay
Switching contact
230 V AC, max. 6 A (not
floating); cos
ϕ
≥ 0.7
Boiler feedback relay
42 V AC; 1 V < U
≅
42 V;
1 mA < I
≅
100 mA; cos
ϕ
= 1
Thermal actuators
2.7 A max. for 1 s;
200 mA; cos
ϕ
≥ 0.95
Ambient temperature
0 to 50°C
Storage temperature
-20 to +70 °C
Humidity
5 to 93% relative humidity
Radio communication
SRD (868,0...870,0) MHz
RX Class 2
Range
Typically 30 m, one floor
Dimensions
350 x 82 x 52 mm
(W x H x D)
Weight
1 kg
Fuse
Ceramic fuse 5 x 20 mm,
230 V AC; 2.5 A; fast
Material
LOW
Degree of protection
IP30
Fire class
V0
WEEE Directive 2012/19/EU
At the end of the product life dispose of the
packaging and product in a corresponding recycling
centre. Do not dispose of the unit with the usual
domestic refuse. Do not burn the product.
Device and function definition in
accordance with EN 60730-1
• Purpose of the device is temperature controlling
• Device fulfils Protection class 1,
EN60730-1, EN60730-2-9
• Independently installable electronic
control system with fixed installation
• Type of action is Type 1.B (pump relay)
and Type 1.C (thermal actuator)
• Temperature
for ball-thrust hardness test for housing components:
75 °C and
for live parts such as terminals: 125 °C
• EMC emitted interference test at 230 V AC
+10/-15 %, 1750 VA maximum
• Pollution severity is 2
• Rated voltage is 4000 V (corresponding
to Overvoltage category III)
Declaration of conformity
Manufactured for and on behalf of the Environmental
& Energy Solutions Division of Honeywell Technologies
Sàrl, E&ES, Z.A., La Pièce 16, 1180 Rolle, Switzerland
by its Authorised Representative Honeywell Inc.
This supersedes any existing Approvals
information on product literature.
Hereby, Honeywell declares that products listed
below in groups A, B and C are in compliance
with the essential requirements and other relevant
provisions of the following Directives:
A: EMC: 2014/30/EU, LVD: 2014/35/EU
B: R.E.D.: 2014/53/EU (Receiver Category 2)
Max RF power: 25mW
Operating frequency: 868.3MHz (868.0 to 868.6MHz)
C: R.E.D.: 2014/53/EU
Maximum Power: 100mW
Operating frequency: 2.4–2.458Ghz (Wi-Fi)
The full texts of the EU Declarations of
Conformity are available at the following
Internet address:
http://hwll.co/DoC
Note for non-EU countries:
This product may only be used
if operation in the 868 MHz
frequency band is permissible.
!
Technical data