HCE80(R) / HCC80(R)
Mounting and operation
5
The underfloor heating controller
offers the following functions:
• 5 controllable temperature zones, extendable to 8
• Up to 3 thermal actuators can be connected per zone
• Normally open or normally closed
thermal actuators can be used
• Integrated pump relay
• Boiler feedback
– Analog (only HCE80/HCC80)
– Integrated relay with floating contact
42 V AC/VDC (only at HCE80R, HCC80R)
– Wireless via relay BDR91
• Underfloor heating controller can be
switched between heating and cooling
• 1 antenna (internal or external) can
be used for 3 controllers
• Rapid installation through screwless
terminals of the thermal actuators
• Intelligent controlling via fuzzy logic
• Simple diagnoses of the wireless transmission
• Operating state display via LEDs
HCE80
HCE80R
HCC80
HCC80R
Antenna
External
External
Internal
Internal
Pump relay
230 V AC internal
230 V AC internal
230 V AC internal
230 V AC internal
Analog output
Available
Not available
Available
Not available
Boiler feedback radio
External with BDR91
External with BDR91
External with BDR91
External with BDR91
Boiler feedback relay
Not available
42 V AC/VDC
Not available
42 V AC/VDC
The pump relay 230 V AC is not floating.
!