![Honeywell H Series Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/honeywell/h-series/h-series_installation-instructions-manual_151844046.webp)
H-SERIES GREEN CLASS NET METER
62-0424-02
46
Lonworks SNVT Types Point Map:
Network Variable
Name
SNVT Type
Description
Units
Green
Net
Meters
nvoKWh_Del
SNVT_count_inc_f Energy delivered
kWh
R
nvoKWh_Rec
SNVT_count_inc_f Energy received
kWh
R
nvoKVarh_Del
SNVT_count_inc_f Reactive energy
delivered
kVARh R
nvoKVarh_Rec
SNVT_count_inc_f Reactive energy
received
kVARh R
nvoReal_Pwr
SNVT_count_inc_f Real power
kW
R
nvoReact_Pwr
SNVT_count_inc_f Reactive power
kVARh R
nvoAppar_Pwr
SNVT_count_inc_f Apparent power
kVARh R
nvoPwr_Fact
SNVT_pwr_fact_f Power factor
% PF
R
nvoCurrent_Total
SNVT_amp_f
Current total
Amps
R
nvoCurrent_Avg
SNVT_amp_f
Current average
Amps
R
nvoVolt_LN
SNVT_volt_f
Voltage line-neutral
Volts-N R
nvoVolt_LL
SNVT_volt_f
Voltage line-line
Volts-L R
nvoFrequency
SNVT_freq_f
Frequency
Hz
R
nvoPhase_Angle
SNVT_angle_f
Phase angle
Degree R
nvoReal_Pwr_PhA
SNVT_count_inc_f Real power, phase A kW
R
nvoReal_Pwr_PhB
SNVT_count_inc_f Real power, phase B kW
R
nvoReal_Pwr_PhC
SNVT_count_inc_f Real power, phase C kW
R
nvoReact_Pwr_PhA SNVT_count_inc_f Reactive power,
phase A
kVAR
R
nvoReact_Pwr_PhB SNVT_count_inc_f Reactive power,
phase B
kVAR
R
nvoReact_Pwr_PhC SNVT_count_inc_f Reactive power,
phase C
kVAR
R
nvoAppar_Pwr_PhA SNVT_count_inc_f Apparent power,
phase A
kVA
R
nvoAppar_Pwr_PhB SNVT_count_inc_f Apparent power,
phase B
kVA
R
nvoAppar_Pwr_PhC SNVT_count_inc_f Apparent power,
phase C
kVA
R
nvoPwr_Fact_PhA
SNVT_pwr_fact_f Power factor, phase
A
% PF
R
nvoPwr_Fact_PhB
SNVT_pwr_fact_f Power factor, phase
B
% PF
R