H-SERIES GREEN CLASS NET METER
62-0424-02
10
3.0 METER TECHNICAL SPECIFICATIONS
Input Voltage
Configuration
3-wire (Delta) Or 4-wire (Wye)
Mains Voltage Input
Up To 600 VAC RMS Available
Input Power
12 VA Maximum Rating
Current Sensor Rating Up To 3200 Amps RMS AC Available
Power Factor
0.5 Leading Or Lagging
Line Frequency
50-60 Hz
Metering Accuracy
ANSI C12.20
Voltage Operating
Range
+/-10% Of Rated Load
Temperature Range
-20 C To +50 C
Relative Humidity
Range
0-95% Non-condensing
Altitude
2000 Meters Maximum
Voltage Overload
+25% Continuously: +100% For 20 Cycles
Current Sensor
Overload
100% For 1 Minute Without Damaging Meter
Pollution Degree
Degree 2 In Accordance With IEC 664
Installation
(Overvoltage) Category
Category 111
Measurement
Category
Category 111
Enclosure Type
Green heavy duty JIC steel enclosure with padlocking hasp
and mounting flanges for indoor installation
Display Readout
4 Line LCD
Standard Ranges
2-Wire Delta 120 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 120/208 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 120/240 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 277/480 VAC: 100, 200, 400, 800,1600, 3200 Amp
2-Wire Wye 277 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 400 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 480 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 600 VAC: 100, 200, 400, 800,1600, 3200 Amp