![Honeywell H Series Скачать руководство пользователя страница 3](http://html.mh-extra.com/html/honeywell/h-series/h-series_installation-instructions-manual_151844003.webp)
H-SERIES GREEN CLASS NET METER
3
62-0424-02
1.0 INTRODUCTION
The Honeywell Green Class Net meter is a 3-phase meter with communications. The
device is used to monitor electric power usage of individual loads after the utility meter
and store kW and kVAR data for automatic meter reading. The Green Class Net meter
is dual protocol capable and provides both RS485 and Ethernet communications.
Installation must only be performed by qualified personnel and in accordance with
these instructions and all applicable local and national electrical codes. Honeywell and
its representatives assume no responsibility for damages or injury resulting from the
improper installation of this meter.
Verify the input voltage rating and configuration on the unit panel label to ensure that it
is suitable for the intended electrical service. For example, Green Class Net meters
labeled for 120/208V service MUST NOT be installed on service feeds of 277/480 volts
or 347/600 and vice versa (see chart below):
Verify that the Green Class Net meter’s current sensors are sized suitably for the load
to be monitored. Compare the color of the arrows on the current sensors to the chart
below to confirm the correct current sensor is being used.
Meter Labeled:
Works On:
120V
120V, Single Phase
120/240V
120/240V, Single Phase
277V
277V, Single Phase
208V
208V, Three Phase
240V
240V, Three Phase
400V (380V,415V)
400V, Three Phase
480V
480V, Three Phase
600V
600V, Three Phase
Sensor Arrow Color Code
Sensor Rating
Brown
100 A
Red
200 A
Yellow
400 A
Black
800 A
Blue
1600 A
White/Black 3200
A