6.8.5 Baud Rate Selection
The communication baud rate is selected by means of a jumper on the circuit board.
Baud Rate is applicable for EZ-7 PROTOCOLS. Factory default is 9600 for EZ-7.
Maximum baud rate is 19200 for EZ-7. Minimum baud rate is 9600.
1. Select 9600 when using the Green Class Net meter with a modem or with EZ-7
meters.
2. The baud rate on the meter must always match the baud rate selected in the E-
Mon Energy software; otherwise, communications will not work.
3. After a baud rate change, press CPU Reset to register the change.
4. All meters in the daisy-chain circuit must be set at the same baud rate.
5. The DIP switch is located above the RS-485 terminals.
6. Using other than 9600 BAUD will reduce the maximum cable length allowed for
communication.
NOTE: USE ONLY POSITIONS 3 AND 4 - DO NOT CHANGE ANY OTHER
POINTS.
The selections are noted below.
Fig. 14. Baud Rate Selection.
3
4
Baud rate
ON ON
9600 (EZ-7)