GSMX4G
/
GSMXCN4G Installation and Setup Guide
– 9 –
Mounting
Hole (2)
Hole
Cap
Wiring
Access
Hole
GSMX4G-006-V0
To ECP Bus
on control panel
circuit board.
ECP Cable
Audio
Connector
PANEL DATA OUT - Yellow
AUX PWR (+12V) - Red
GND - Black
PANEL DATA IN - Green
4.
Connect the ECP cable to the communicator circuit board. When
mounting the communicator off the cabinet, the length of the sup-
plied ECP cable will have to be spliced to a four-wire extender cable.
Ensure the splices are located within the communicator's
enclosure.
Use the table below to determine the minimum wire gauge for the
extender cable.
Minimum Wire Gauge
Distance from Control Panel
#22
75 ft (23m)
#20
120 ft (37m)
#18
170 ft (52m)
#16
270 ft (82m)
5.
Route the wires through the rear wiring access hole or bottom
knockout on the communicator. Continue routing the wiring to the
control panel. A control panel knockout that is presently used can be